LS-B Series MPPT Charge Controller Protocol

Modbus Register Address List

Version: 1.1
Company: Beijing Epsolar Technology Co., Ltd.

Notes

  1. The controller’s default ID is 1 and can be modified using PC software (Solar Station Monitor) or the MT50 remote meter.
  2. Serial communication parameters: 115,200 bps baud rate, 8 data bits, 1 stop bit, no parity, no handshaking.
  3. Register addresses are in hexadecimal format.
  4. For 32-bit data (e.g., power), the L and H registers represent the low and high 16-bit values, respectively. For example, a charging input rated power of 3000 W (multiplied by 100) results in register 0x3002 holding 0x93F0 and register 0x3003 holding 0x0004.

Rated Data (Read-Only) Input Registers

Variable Name Address Description Unit Scale
Rated PV input voltage 3000 PV array rated voltage V 100
Rated PV input current 3001 PV array rated current A 100
Rated PV input power (low) 3002 PV array rated power (low 16 bits) W 100
Rated PV input power (high) 3003 PV array rated power (high 16 bits) W 100
Rated battery voltage 3004 Battery voltage V 100
Rated charging current 3005 Rated charging current to battery A 100
Rated charging power 3006 Rated charging power to battery W 100
Reserved 3007 W 100
Charging mode 3008 0001H: PWM
Rated load current 300E Rated load output current A 100

Real-Time Data (Read-Only) Input Registers

Variable Name Address Description Unit Scale
PV input voltage 3100 PV array voltage V 100
PV input current 3101 PV array current A 100
PV input power (low) 3102 PV array power (low 16 bits) W 100
PV input power (high) 3103 PV array power (high 16 bits) W 100
Battery voltage 3104 Battery voltage V 100
Battery charging current 3105 Battery charging current A 100
Battery charging power (low) 3106 Battery charging power (low 16 bits) W 100
Battery charging power (high) 3107 Battery charging power (high 16 bits) W 100
Load voltage 310C Load voltage V 100
Load current 310D Load current A 100
Load power (low) 310E Load power (low 16 bits) W 100
Load power (high) 310F Load power (high 16 bits) W 100
Battery temperature 3110 Battery temperature °C 100
Controller internal temperature 3111 Internal case temperature °C 100
Power component temperature 3112 Heat sink temperature of power components °C 100
Battery SOC 311A Battery state of charge (remaining capacity percentage) % 100
Remote battery temperature 311B Battery temperature from remote sensor °C 100
System rated voltage 311D Current system rated voltage (1200 = 12 V, 2400 = 24 V) V 100

Real-Time Status (Read-Only) Input Registers

Variable Name Address Description
Battery status 3200 D3-D0: 00H: Normal, 01H: Overvoltage, 02H: Undervoltage, 03H: Low Voltage Disconnect, 04H: Fault
D7-D4: 00H: Normal, 01H: Over Temperature (above warning threshold), 02H: Low Temperature (below warning threshold)
D8: Battery internal resistance: 1 = Abnormal, 0 = Normal
D15: Rated voltage identification: 1 = Incorrect, 0 = Correct
Charging equipment status 3201 D15-D14: Input voltage status: 00 = Normal, 01 = No power, 02H = High voltage, 03H = Voltage error
D13: Charging MOSFET short
D12: Charging or anti-reverse MOSFET short
D11: Anti-reverse MOSFET short
D10: Input overcurrent
D9: Load overcurrent
D8: Load short
D7: Load MOSFET short
D4: PV input short
D3-D2: Charging status: 00 = No charging, 01 = Float, 02 = Boost, 03 = Equalization
D1: 0 = Normal, 1 = Fault
D0: 1 = Running, 0 = Standby

Statistical Parameters (Read-Only) Input Registers

Variable Name Address Description Unit Scale
Maximum PV voltage today 3300 Refreshed daily at 00:00 V 100
Minimum PV voltage today 3301 Refreshed daily at 00:00 V 100
Maximum battery voltage today 3302 Refreshed daily at 00:00 V 100
Minimum battery voltage today 3303 Refreshed daily at 00:00 V 100
Consumed energy today (low) 3304 Cleared daily at 00:00 kWh 100
Consumed energy today (high) 3305 Cleared daily at 00:00 kWh 100
Consumed energy this month (low) 3306 Cleared on the first day of the month kWh 100
Consumed energy this month (high) 3307 Cleared on the first day of the month kWh 100
Consumed energy this year (low) 3308 Cleared on January 1 kWh 100
Consumed energy this year (high) 3309 Cleared on January 1 kWh 100
Total consumed energy (low) 330A kWh 100
Total consumed energy (high) 330B kWh 100
Generated energy today (low) 330C Cleared daily at 00:00 kWh 100
Generated energy today (high) 330D Cleared daily at 00:00 kWh 100
Generated energy this month (low) 330E Cleared on the first day of the month kWh 100
Generated energy this month (high) 330F Cleared on the first day of the month kWh 100
Generated energy this year (low) 3310 Cleared on January 1 kWh 100
Generated energy this year (high) 3311 Cleared on January 1 kWh 100
Total generated energy (low) 3312 kWh 100
Total generated energy (high) 3313 kWh 100
CO2 reduction (low) 3314 1 kWh saved = 0.997 kg CO2 or 0.272 kg carbon reduction Ton 100
CO2 reduction (high) 3315 Ton 100
Net battery current (low) 331B Charging current minus discharging current (positive = charging, negative = discharging) A 100
Net battery current (high) 331C A 100
Battery temperature 331D Battery temperature °C 100
Ambient temperature 331E Ambient temperature °C 100

Setting Parameters (Read-Write) Holding Registers

Variable Name Address Description Unit Scale
Battery type 9000 0000H: User-defined, 0001H: Sealed, 0002H: GEL, 0003H: Flooded
Battery capacity 9001 Rated battery capacity Ah
Temperature compensation coefficient 9002 Range: 0–9 mV/°C/2V 100
High voltage disconnect 9003 V 100
Charging limit voltage 9004 V 100
Overvoltage reconnect 9005 V 100
Equalization voltage 9006 V 100
Boost voltage 9007 V 100
Float voltage 9008 V 100
Boost reconnect voltage 9009 V 100
Low voltage reconnect 900A V 100
Undervoltage recovery 900B V 100
Undervoltage warning 900C V 100
Low voltage disconnect 900D V 100
Discharging limit voltage 900E V 100
Real-time clock (seconds/minutes) 9013 D7–D0: Seconds, D15–D8: Minutes (write Year, Month, Day, Minutes, Seconds simultaneously)
Real-time clock (hours/day) 9014 D7–D0: Hours, D15–D8: Day
Real-time clock (month/year) 9015 D7–D0: Month, D15–D8: Year
Equalization charging cycle 9016 Interval for auto-equalization charging Days
Battery temperature warning upper limit 9017 °C 100
Battery temperature warning lower limit 9018 °C 100
Controller internal temperature upper limit 9019 °C 100
Controller internal temperature recovery 901A System resumes when temperature drops below this value °C 100
Power component temperature upper limit 901B Charging/discharging stops if power component temperature exceeds this value °C 100
Power component temperature recovery 901C System resumes when power component temperature drops below this value °C 100
Line impedance 901D Resistance of connected wires 100
Nighttime threshold voltage (NTTV) 901E PV voltage below this value indicates sundown V 100
Night detection delay 901F Duration PV voltage must remain below NTTV to detect nighttime Minutes
Daytime threshold voltage (DTTV) 9020 PV voltage above this value indicates sunrise V 100
Day detection delay 9021 Duration PV voltage must remain above DTTV to detect daytime Minutes
Load control mode 903D 0000H: Manual, 0001H: Light ON/OFF, 0002H: Light ON + Timer, 0003H: Time Control
Load timer 1 duration 903E Load output timer 1 duration (D15–D8: Hours, D7–D0: Minutes)
Load timer 2 duration 903F Load output timer 2 duration (D15–D8: Hours, D7–D0: Minutes)
Load timing 1 (on) 9042 Load on/off timing (seconds) Seconds
9043 Load on/off timing (minutes) Minutes
9044 Load on/off timing (hours) Hours
Load timing 1 (off) 9045 Load on/off timing (seconds) Seconds
9046 Load on/off timing (minutes) Minutes
9047 Load on/off timing (hours) Hours
Load timing 2 (on) 9048 Load on/off timing (seconds) Seconds
9049 Default night duration (D15–D8: Hours, D7–D0: Minutes) Minutes
904A Default night duration (hours) Hours
Load timing 2 (off) 904B Load on/off timing (seconds) Seconds
904C Load on/off timing (minutes) Minutes
904D Load on/off timing (hours) Hours
Night duration 9065 Total night duration
Battery rated voltage code 9067 0: Auto-recognize, 1: 12 V, 2: 24 V
Load timing control selection 9069 Load timing period: 0 = One timer, 1 = Two timers
Default load state (manual mode) 906A 0: Off, 1: On
Equalization duration 906B Typically 60–120 minutes Minutes
Boost duration 906C Typically 60–120 minutes Minutes
Discharging percentage 906D Battery capacity percentage when discharging stops (typically 20%–80%) % 100
Charging percentage 906E Depth of charge (typically 20%–100%) % 100
Battery management mode 9070 0: Voltage compensation, 1: SOC

Coils (Read-Write)

Variable Name Address Description
Manual load control 2 In manual mode: 1 = On, 0 = Off
Load test mode 5 1 = Enable, 0 = Disable (normal)
Force load on/off 6 1 = On, 0 = Off (for temporary load testing)

Discrete Inputs (Read-Only)

Variable Name Address Description
Controller over-temperature 2000 1 = Temperature exceeds protection threshold, 0 = Normal
Day/night status 200C 1 = Night, 0 = Day

RJ-45 Port Pin Definitions

Pin Description
1, 2 Not connected
3, 4 RS-485 A
5, 6 RS-485 B
7, 8 Ground

Notes

  1. To enhance communication quality, ground pins 7 and 8 (connected to the battery’s negative terminal) may be used if needed. Ensure proper handling of common ground issues among connected devices.
  2. For safety, do not use pins 1 and 2.