@@ -51,7 +51,7 @@ That being said, these koji rooms were effective - and even though they lack mos
5151

5252
## Modern Koji Rooms
5353

54-
Modern koji rooms solved all the problems with old koji-rooms, and starting in the 1950s, all breweries quickly renovated to employ the following design features, which I'll quickly summarize:
54+
Modern koji-rooms solved all the problems with old koji-rooms, and starting in the 1950s, all breweries quickly renovated to employ the following design features, which I'll quickly summarize:
5555

5656
1. Electric heaters (often wall-mounted panel heaters or wall-mounted heating coils)
5757
2. Modern insulation (fibreglass, mineral wool, PVC foam, styrofoam, or polyurethane foam)
@@ -80,6 +80,7 @@ The table below provides all the key information needed to properly design a koj
8080

8181
**Table 1 - Design parameters for common koji substrates [4]**
8282

83+
8384
| Substrate | Initial Moisture<br /> (%) | Initial Specific Volume<br /> (L/kg) | Peak Heat Generation <br />(kJ/kg-dry/h) | Total Heat Generation<br /> (kJ/kg-dry) |
8485
| -------------------------------------- | -------------------------: | -----------------------------------: | ---------------------------------------: | ---------------------------------------: |
8586
| Wheat bran & rice husk koji (1:1) | 50-55 | 9.2 | 158 | 1990-2620 |
@@ -121,7 +122,7 @@ The koji room's ventilation must be sufficient to remove excess heat, humidity,
121122

122123
Let's demonstrate which of these three design criteria is our limit, using our example.
123124

124-
First, consider the requirements for **heat removal**. We can show that our 300kg of rice-koji at *hiki-komi* has a dry weight of 195kg, and will generate 1623W at the peak of its metabolism (see Appendix - [Step 4](#step-4---determine-the-ventilation-requirements-for-heat-removal)). Our conductive heat losses were calculated to be 764W, so we know that ventilation for heat removal must equal 859W by exchanging indoor air with cold, outdoor air. This requires a ventilation rate of 41m³/h.
125+
First, consider the requirements for **heat removal**. We can show that our 300kg of rice-koji at *hiki-komi* has a dry weight of 195kg, and will generate 1623W at the peak of its metabolism (see Appendix - [Step 4](#step-4---determine-the-ventilation-requirements-for-heat-removal)). Our conductive heat losses were calculated to be 764W, so we know that ventilation for heat removal must equal 859W by exchanging indoor air with cold, outdoor air. This requires a ventilation rate of **41m³/h**.
125126

126127

127128
![Heat balance of the koji room with ventilation sized for heat removal](/assets/images/koji_room/02kojiroomheat.png)
@@ -209,7 +210,7 @@ Some other equipment worth mentioning, primarily used to reduce labour costs:
209210

210211
#### Air shooter
211212

212-
A common way to transfer steamed substrate into the koji room, and finished koji out of the room, is to use a device called an *air shooter*. This is a a Japanese *wasei-eigo* term for what would commonly be called a pneumatic conveying system consisting of: 1) a blower 2) a feed assembly consisting of a hopper, rotary valve, and solids-conveying educator, 3) a bunch of hose, and 4) an outlet cyclone (optional). These are much faster than transferring substrate by hand.
213+
A common way to transfer steamed substrate into the koji room, and finished koji out of the room, is to use a device called an *air shooter*. This is a Japanese *wasei-eigo* term for what would commonly be called a pneumatic conveying system consisting of: 1) a blower 2) a feed assembly consisting of a hopper, rotary valve, and solids-conveying educator, 3) a bunch of hose, and 4) an outlet cyclone (optional). These are much faster than transferring substrate by hand.
213214

214215
![](/assets/images/koji_room/Airshooter.png){:height="550" .center}
215216
*Top: a schematic of an air-shooter (pneumatic conveying system), bottom-left: feed assembly, bottom-right: blower. From [1] and Toyo Shokai Co., Ltd.*
@@ -283,9 +284,11 @@ Air flows in this post are using a dry air basis at 30°C / 70% RH (indoor condi
283284
#### Step 2 - Determine the koji amount, dry weight, and room dimensions.
284285

285286
The weight of steamed rice at inoculation (hiki-komi) will be 300kg. If the unsoaked white rice has a moisture of 13%, and the water absorption ratio at inoculation is 34%, the actual water content of the koji is:
287+
286288
$$
287289
\%Total\ moisture = \frac{Total\ Water}{Total\ Weight}=\frac{13\%+34\%}{100\%+34\%} = 35.1\%
288290
$$
291+
289292
This is in agreement with Table 1. Thus the dry weight of the steamed rice is 194.8kg and its peak heat generation is 5843kJ/h or 1623W (unit conversions not shown).
290293

291294
Let the depth of koji be 5cm. Based on Table 1, 300kg of steamed rice will occupy approximately 660L or 0.66m³ in volume and require a table with an area of 13.2 square meters (geometric calculations not shown). Let's select a 5.3m x 2.5m table. To allow for clearance and the storage of other items, let's select a room of 8m (L) x 5m (W). Finally, a ceiling height of 2.0-2.2m is standard - we will select 2.2m (H).
@@ -321,15 +324,19 @@ Where,
321324
- $RSI_n$ = insulation R value (metric RSI value), equivalent to x/k (m-K/W)
322325

323326
Select a 4-inch polyurethane insulation with a total metric RSI value of 4.24 (m-K/W). We'll use a convective heat transfer coefficient of 8.0 W/m-K on both sides of the wall. Now, we can find the overall heat transfer coefficient:
327+
324328
$$
325329
\frac{1}{U} = \frac{1}{8}+4.24 +\frac{1}{8} \text{ (SI Units)}\\
326330
U = 1.3W/m^2\cdot K
327331
$$
332+
328333
As well as the heat losses through the wall:
334+
329335
$$
330336
Q = (1.3W/m^2\cdot K)(137.2m^2 )(30^\circ C-5^\circ C) \\
331337
Q = 764W
332338
$$
339+
333340
Heat flux is simply heat transfer divided by area, or Q/A. In 1-D steady state heat transfer, this term is constant no matter where you are along the wall.
334341
$$
335342
\frac{Q}{A} = h(T_1 - T_w)
@@ -339,30 +346,36 @@ Where,
339346
$T_w$ is the temperature at the koji room wall
340347

341348
If we solve for the wall temperature:
349+
342350
$$
343351
763W = (8W/m^2\cdot K)(137.2m^2)(30^\circ C-T_w)\\
344352
T_w = 29.3^\circ C
345353
$$
354+
346355
This is well above the dew point of our koji room, so no condensation is expected.
347356

348357
----
349358

350359
#### Step 4 - Determine the ventilation requirements for heat removal
351360

352361
This is a heat balance on the koji room:
362+
353363
$$
354364
Q_{koji} = Q_{wall} + Q_{vent}
355365
$$
366+
356367
Where,
357368

358369
- $Q_{koji}$ - peat heat generation from koji (W)
359370
- $Q_{wall}$ - heat losses through the wall (W) (from Step 3)
360371
- $Q_{vent}$ - heat removed via ventilation (W)
361372

362373
Heat removed by ventilation is simply flow rate times the difference in the air enthalpy in and out of the system:
374+
363375
$$
364376
Q_{vent} = \dot{m}(H_1 -H_2)
365377
$$
378+
366379
Where,
367380

368381
- ṁ = mass flow rate of air (kg dry air/s)
@@ -388,6 +401,7 @@ $$
388401
\text{Water generated by koji} = \text{Water removed by ventilation}\\
389402
\frac{FQ_{koji}}{\Delta H_{vap,T_1}}=\dot{m}(W_1-W_2)
390403
$$
404+
391405
Where
392406

393407
- F = fraction of heat generated by koji removed by evaporative cooling (0.8)
@@ -396,10 +410,12 @@ Where
396410
- W₂ = outdoor absolute humidity (g water / kg dry air )
397411

398412
Our mass balance becomes:
413+
399414
$$
400415
\frac{(0.8)(1623W)}{2429.8J/g} = \dot{m}(18.8\text{g water/kg dry air} - 2.7\text{g water/kg dry air})\\
401416
m = 0.03317\text{kg dry air/s}
402417
$$
418+
403419
We know its specific volume is 0.885 m³/kg dry air so the ventilation rate is 105.7m³/h (indoor basis).
404420

405421
----
@@ -417,16 +433,20 @@ $$
417433
$$
418434

419435
We can convert to volumetric CO₂ generation using the ideal gas law:
436+
420437
$$
421438
\dot{V}_{CO_2,koji}=\frac{\dot{n}RT}{P}\\
422439
\dot{V}_{CO_2,koji} =12.2\text{mol}\ CO_2 /h\times\frac{(8.314J\text{mol}^{-1}K^{-1})(303.15K)}{101300Pa}\\
423440
\dot{V}_{CO_2,koji} = 0.304m^3/h
424441
$$
442+
425443
Mass balance on carbon dioxide:
444+
426445
$$
427446
CO_2 \text{ generated by koji} = CO_2 \text{ removed by ventilation}\\
428447
\dot{V}_{CO_2,koji} =\dot{V}(C_1-C_2)
429448
$$
449+
430450
Where,
431451

432452
- $m_{CO₂,koji}$ = CO₂ generated by koji (m³/h)
@@ -435,6 +455,7 @@ Where,
435455
- C₂ = concentration of CO₂ outside (fraction)
436456

437457
Our mass balance becomes:
458+
438459
$$
439460
0.304m^3/h = \dot{V}(0.004500-0.000500)\\
440461
\dot{V}=75.9m^3/h
@@ -445,9 +466,11 @@ $$
445466
#### Step 7 - Determine the heating requirements
446467

447468
Heat balance on the koji room:
469+
448470
$$
449471
Q_{koji}+Q_{heater}=Q_{wall}+Q_{vent}
450472
$$
473+
451474
Where $Q_{heater}$ = heat required by the heater
452475

453476
Our heat balance becomes: