class: middle, center, title-slide count: false
Lecture 7: Voltage regulation and voltage instability
Louis Wehenkel
L.Wehenkel@uliege.be
- Voltage regulation and reactive power compensation in EHV grids
- Voltage instability and voltage collapse
- EHV Voltage control and reactive power compensation devices
- Voltage control in the distribution systems
- Likely impact of the energy transition on these topics
This lecture expands on Chapter 10 from the Ned Mohan's book.
class: middle
We want to transfer some active power
Neglecting line resistance
where
Notice that in EHV (transmission systems) at 100kV-750kV: $X_L/R_L \approx 10-30$.
In practice we also want the voltage magnitude at both ends to be
close to
We see that under these conditions
Part of this reactive power is already produced by the capacitance of the line itself.
The rest, depending on the
amount of power
The voltage profile
If
If
In this latter case (e.g. cables, or very long transmission lines), the insulation capability may impose reactive power compensation 'along' the line, e.g. in the form of shunt reactors.
class: middle
Consider the case of Figure (a) below, assuming an ideal voltage source and neglecting line resistance and line capacitance:
From Figure (b) above, we see that (for each PF) there is a maximum value of
-
the high voltage solution, which is stable
-
the low voltage solution, which is unstable
NB: in our notations:
NB: in our notations:
Setting
The load chacteristic (black curve) is defined by
The operating point is obtained as the intersection of the nose curve and the load characteristic.
Increasing the load essentially consists in adding further loads in parallel with already existings ones, and thus results in a decrease of the total load resistance.
The red curve corresponds to
Beyond this level, further decreasing the load resistance
We the load power increases, the source generator must supply more and more reactive power.
The red "PV-curve" corresponds to the source generator reaching its excitation current limit: the ideal voltage source is replaced by adding its synchronous reactance in series with the line.
Imagine that
The operating point "instantaneously" switches to the intersection of the load characteristic and the new system characteristic, leading to a significant drop in voltage and received power.
After the "instantaneous" (dashed arrow) switch of the operating point, the load power has well decreased.
Subsequently, the load active power tries to restore itself to the level at which it was before the line tripping (plain arrows).
This restoration process can yield voltage collapse as shown on the graph. Its speed depends on the nature of the load restoration process.
-
Fast (less than a minute): automatic controls acting on electric loads, such as speed control of trains, elevators, and in general motors
-
Medium speed (a few minutes): automatic controls of transformer ratios (taps) acting on the voltage level in the distribution system (since most loads are voltage sensitive)
-
Slow (tens of minutes): thermostatic loads, manual 'human-driven' feedback mechanisms
NB: in practice, the various voltage instability and load-restoration mechanisms may act in combination.
NB-bis: although we made a 2-bus analysis, the same phenomena are observed in multi-bus systems.
NB-ter: voltage instability has led to several large-scale power system blackouts.
-
Increasing the distance (
$X_L$ ) between supply and demand -
Reducing the reactive power generation reserves
-
Faster load restoration mechanisms, slower reactive power controls
-
Switchable reactive power compensation devices (capacitors, inductors)
-
Ensuring the availability of reactive power reserves close to load areas
-
Ad hoc and clever voltage control schemes
class: middle
- Voltage controls of synchronous generators and synchronous condensers
- Switching of reactive compensation devices (capacitors and inductors)
- Power electronics empowered devices: SVC, STATCOM, HVDC, TCSC
- Preventive control
- Must-run generators (days/hours ahead in time)
- Setting of control device parameters (weeks/months ahead in time)
- Installation of reactive compensation devices (months/years ahead in time)
- Primary/Secondary/Tertiary voltage control
- Fast backup generation unit start-up
- On-load transformer tap changer blocking
- Under voltage load-shedding
class: middle
Distribution systems are (typically) radial, operate at lower voltage levels, and have no synchronous generation installed.
Voltage is mostly controlled by using tap-changing transformers. Wires copper sections are chosen in order to cover peak demand along the feeder.
Notice that in MV-LV (distribution systems) at 200V-20kV: $X_L/R_L \approx 0.2 - 1$
class: middle
-
Increasing difficulties
-
Fewer synchronous generators in operation at the transmission level
-
Higher variability of flows and flow-directions at the distribution and transmission level
-
New 'high-tech' opportunities
- Power electronics
- Smart-grid technologies
- Mohan, Ned. Electric power systems: a first course. John Wiley & Sons, 2012.
- Van Cutsem, Thierry and Vournas, Costas. Voltage stability of electric power systems. Kluwer Academic Publishers, 1998
- Weedy, B.M. et al. Electric power systems. John Wiley & Sons, 2012
class: end-slide, center count: false
The end.












