Skip to content

EM300-DI Payload Codec Pulse #69

@Keelan

Description

@Keelan

Shouldn't the below be pulse not water? If i've configured the sensor as counter/pulse but in the payload JSON the pulse is missing and in bacnet the pulse value is always 0, but i see the water go up. The pulses i am receiving to the sensor are gas and electrical not water. So makes sense its called pulse rather than water

decoded.water = readFloatLE(bytes.slice(i + 4, i + 8));

What i changed my codec too:
decoded.pulse = readFloatLE(bytes.slice(i + 4, i + 8));

Also in the pulse context do we need the following?
decoded.water_conv = readUInt16LE(bytes.slice(i, i + 2)) / 10;

We already have
decoded.pulse_conv = readUInt16LE(bytes.slice(i + 2, i + 4)) / 10;

Similarly, do we need pulse_conv in the water alarm section?

from

        // WATER ALARM
        else if (channel_id === 0x85 && channel_type === 0xe1) {
            decoded.water_conv = readUInt16LE(bytes.slice(i, i + 2)) / 10;
            decoded.pulse_conv = readUInt16LE(bytes.slice(i + 2, i + 4)) / 10;
            decoded.water = readFloatLE(bytes.slice(i + 4, i + 8));
            decoded.water_alarm = readWaterAlarm(bytes[i + 8]);
            i += 9;
        }

to

        // WATER ALARM
        else if (channel_id === 0x85 && channel_type === 0xe1) {
            decoded.water_conv = readUInt16LE(bytes.slice(i, i + 2)) / 10;
            decoded.water = readFloatLE(bytes.slice(i + 4, i + 8));
            decoded.water_alarm = readWaterAlarm(bytes[i + 8]);
            i += 9;
        }