Issue/note about migrating from Honewell MHK1 thermostats #284

@Mortimer452

Description

@Mortimer452

Not necessarily an "issue" but worth noting that there is a setting that must be changed from the Honeywell MHK1 controller before switching over to the ESP32/Mitsubishi2MQTT device.

In the MHK1 installation manual page 7 lists the installer setup tables. Setting# 173 is set to 1 (Sense at Remote Controller) by default which tells the unit to read the current room temperature from the controller rather than the indoor unit itself.

If this setting is not changed to 0 (Sense at Indoor Unit), after installing the ESP32 board, the air handler is forever "stuck" thinking the room temperature is whatever value was last read from the MHK1 thermostat. For example, if your MHK1 set temp was 68 and the room temp was 64 when you replaced the MHK1, the ESP32 thinks the room temp is 64 forever, continuously blasting the heat trying to get it up to the set temp of 68 which it never reads.

The workaround is, before removing the MHK1 and RedLink adapter:

  • Press and hold the FAN and TEMP UP buttons for ~5 seconds to get into the installer settings.
  • Press "Next" until setting 173 appears
  • Press the DOWN TEMP button to ensure this setting is set to 0
  • Press Done to save the setting