Description

@Chris3773

When the low battery warning is triggered the ups.status doesn't update to LB and stays on OB, DISCHRG. The warning is triggered and is visible through the Eaton Network-M3 web UI, but the status is never updated for NUT. I have tested with low the warning trigger at 5% with 0 runtime and 5% with 300 runtime with the same results.

Since the ups.status isn't set to LB status the shutdown is never triggered.

OS: pfSense 24.03-RELEASE
Nut Version: 2.8.2
UPS: Eaton 5PX 3000 RT2U G2 - 1.10.0019
Network Card: Eaton Network-M3 - 1.0.4
Driver: SNMPv3

Metadata

Metadata

Labels

EatonFreeBSDissues related to FreeBSD and its derivatives (including pfSense)Incorrect or missing readingsOn some devices driver-reported values are systemically off (e.g. x10, x0.1, const+Value, etc.)SNMPimpacts-release-2.8.2Issues reported against NUT release 2.8.2 (maybe vanilla or with minor packaging tweaks)