1 | 1 | """Data acquisition script that continuously acquires analog input data."""  | 
2 | 2 | 
 
  | 
 | 3 | +import time  | 
3 | 4 | from pathlib import Path  | 
4 | 5 | 
 
  | 
5 | 6 | import nidaqmx  | 
6 |  | -from nidaqmx.constants import AcquisitionType  | 
 | 7 | +from nidaqmx.constants import (  | 
 | 8 | +    AcquisitionType,  | 
 | 9 | +    TerminalConfiguration,  | 
 | 10 | +    CJCSource,  | 
 | 11 | +    TemperatureUnits,  | 
 | 12 | +    ThermocoupleType,  | 
 | 13 | +    LoggingMode,  | 
 | 14 | +    LoggingOperation,  | 
 | 15 | +)  | 
7 | 16 | 
 
  | 
8 | 17 | import nipanel  | 
9 | 18 | 
 
  | 
10 | 19 | panel_script_path = Path(__file__).with_name("nidaqmx_continuous_analog_input_panel.py")  | 
11 | 20 | panel = nipanel.create_panel(panel_script_path)  | 
12 | 21 | 
 
  | 
13 |  | -# How to use nidaqmx: https://nidaqmx-python.readthedocs.io/en/stable/  | 
14 |  | -with nidaqmx.Task() as task:  | 
15 |  | -    task.ai_channels.add_ai_voltage_chan("Dev1/ai0")  | 
16 |  | -    task.ai_channels.add_ai_thrmcpl_chan("Dev1/ai1")  | 
17 |  | -    task.timing.cfg_samp_clk_timing(  | 
18 |  | -        rate=1000.0, sample_mode=AcquisitionType.CONTINUOUS, samps_per_chan=3000  | 
19 |  | -    )  | 
20 |  | -    panel.set_value("sample_rate", task._timing.samp_clk_rate)  | 
21 |  | -    task.start()  | 
 | 22 | +try:  | 
22 | 23 |     print(f"Panel URL: {panel.panel_url}")  | 
23 |  | -    try:  | 
24 |  | -        print(f"Press Ctrl + C to stop")  | 
25 |  | -        while True:  | 
26 |  | -            data = task.read(  | 
27 |  | -                number_of_samples_per_channel=1000  # pyright: ignore[reportArgumentType]  | 
 | 24 | +    print(f"Waiting for the 'Run' button to be pressed...")  | 
 | 25 | +    print(f"(Press Ctrl + C to quit)")  | 
 | 26 | +    while True:  | 
 | 27 | +        panel.set_value("run_button", False)  | 
 | 28 | +        while not panel.get_value("run_button", False):  | 
 | 29 | +            time.sleep(0.1)  | 
 | 30 | + | 
 | 31 | +        # How to use nidaqmx: https://nidaqmx-python.readthedocs.io/en/stable/  | 
 | 32 | +        with nidaqmx.Task() as task:  | 
 | 33 | +            task.ai_channels.add_ai_voltage_chan(  | 
 | 34 | +                physical_channel="Dev1/ai0",  | 
 | 35 | +                min_val=panel.get_value("voltage_min_value", -5.0),  | 
 | 36 | +                max_val=panel.get_value("voltage_max_value", 5.0),  | 
 | 37 | +                terminal_config=panel.get_value(  | 
 | 38 | +                    "terminal_configuration", TerminalConfiguration.DEFAULT  | 
 | 39 | +                ),  | 
 | 40 | +            )  | 
 | 41 | +            task.ai_channels.add_ai_thrmcpl_chan(  | 
 | 42 | +                "Dev1/ai1",  | 
 | 43 | +                min_val=panel.get_value("thermocouple_min_value", 0.0),  | 
 | 44 | +                max_val=panel.get_value("thermocouple_max_value", 100.0),  | 
 | 45 | +                units=panel.get_value("thermocouple_units", TemperatureUnits.DEG_C),  | 
 | 46 | +                thermocouple_type=panel.get_value("thermocouple_type", ThermocoupleType.K),  | 
 | 47 | +                cjc_source=panel.get_value(  | 
 | 48 | +                    "thermocouple_cjc_source", CJCSource.CONSTANT_USER_VALUE  | 
 | 49 | +                ),  | 
 | 50 | +                cjc_val=panel.get_value("thermocouple_cjc_val", 25.0),  | 
 | 51 | +            )  | 
 | 52 | +            task.timing.cfg_samp_clk_timing(  | 
 | 53 | +                rate=panel.get_value("sample_rate_input", 1000.0),  | 
 | 54 | +                sample_mode=AcquisitionType.CONTINUOUS,  | 
 | 55 | +                samps_per_chan=panel.get_value("samples_per_channel", 3000),  | 
28 | 56 |             )  | 
29 |  | -            panel.set_value("voltage_data", data[0])  | 
30 |  | -            panel.set_value("thermocouple_data", data[1])  | 
31 |  | -    except KeyboardInterrupt:  | 
32 |  | -        pass  | 
33 |  | -    finally:  | 
34 |  | -        task.stop()  | 
 | 57 | +            task.in_stream.configure_logging(  | 
 | 58 | +                file_path=panel.get_value("tdms_file_path", "data.tdms"),  | 
 | 59 | +                logging_mode=panel.get_value("logging_mode", LoggingMode.OFF),  | 
 | 60 | +                operation=LoggingOperation.OPEN_OR_CREATE,  | 
 | 61 | +            )  | 
 | 62 | +            panel.set_value("sample_rate", task._timing.samp_clk_rate)  | 
 | 63 | +            try:  | 
 | 64 | +                print(f"Starting data acquisition...")  | 
 | 65 | +                task.start()  | 
 | 66 | +                panel.set_value("is_running", True)  | 
 | 67 | + | 
 | 68 | +                panel.set_value("stop_button", False)  | 
 | 69 | +                while not panel.get_value("stop_button", False):  | 
 | 70 | +                    data = task.read(  | 
 | 71 | +                        number_of_samples_per_channel=1000  # pyright: ignore[reportArgumentType]  | 
 | 72 | +                    )  | 
 | 73 | +                    panel.set_value("voltage_data", data[0])  | 
 | 74 | +                    panel.set_value("thermocouple_data", data[1])  | 
 | 75 | +            except KeyboardInterrupt:  | 
 | 76 | +                raise  | 
 | 77 | +            finally:  | 
 | 78 | +                print(f"Stopping data acquisition...")  | 
 | 79 | +                task.stop()  | 
 | 80 | +                panel.set_value("is_running", False)  | 
 | 81 | + | 
 | 82 | +except KeyboardInterrupt:  | 
 | 83 | +    pass  | 
0 commit comments