diff --git a/building_energy_standards_data/database_files/system_requirements_fan_power_allowance_pressure_drop_adjustment_189_1.json b/building_energy_standards_data/database_files/system_requirements_fan_power_allowance_pressure_drop_adjustment_189_1.json new file mode 100644 index 0000000..bc3bb15 --- /dev/null +++ b/building_energy_standards_data/database_files/system_requirements_fan_power_allowance_pressure_drop_adjustment_189_1.json @@ -0,0 +1,982 @@ +[ + { + "template": "189.1-2009", + "device": "fully ducted return and/or exhaust air systems", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2009", + "device": "return and/or exhaust airflow control devices", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2009", + "device": "exhaust filters, scrubbers, or other exhaust treatment", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2009", + "device": "particulate filtration credit: merv 9 through 12", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2009", + "device": "particulate filtration credit: merv 13 through 15", + "adjustment_in_wc": 0.9, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2009", + "device": "particulate filtration credit: merv 16 and greater and electronically enhanced filters", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B, clean filter" + }, + { + "template": "189.1-2009", + "device": "carbon and other gas-phase air cleaners", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B, clean filter" + }, + { + "template": "189.1-2009", + "device": "heat recovery device", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2009", + "device": "evaporative humidifier/cooler in series with another cooling coil", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2009", + "device": "sound attenuation section", + "adjustment_in_wc": 0.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2009", + "device": "fume hood exhaust exception", + "adjustment_in_wc": -1, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2011", + "device": "fully ducted return and/or exhaust air systems", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2011", + "device": "fully ducted return and/or exhaust air systems for laboratory and vivarium systems", + "adjustment_in_wc": 2.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2011", + "device": "return and/or exhaust airflow control devices", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2011", + "device": "exhaust filters, scrubbers, or other exhaust treatment", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2011", + "device": "particulate filtration credit: merv 9 through 12", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2011", + "device": "particulate filtration credit: merv 13 through 15", + "adjustment_in_wc": 0.9, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2011", + "device": "particulate filtration credit: merv 16 and greater and electronically enhanced filters", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B, clean filter" + }, + { + "template": "189.1-2011", + "device": "carbon and other gas-phase air cleaners", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B, clean filter" + }, + { + "template": "189.1-2011", + "device": "biosafety cabinet", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2011", + "device": "energy recovery device, other than coil runaround loop for each airstream", + "adjustment_in_wc": -0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": 2.2, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2011", + "device": "coil runaround loop for each airstream", + "adjustment_in_wc": 0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2011", + "device": "evaporative humidifier/cooler in series with another cooling coil", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2011", + "device": "sound attenuation section", + "adjustment_in_wc": 0.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2011", + "device": "exhaust system serving fume hoods", + "adjustment_in_wc": 0.35, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2011", + "device": "laboratory and vivarium exhaust systems in high-rise buildings", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": 0.25, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "189.1-2014", + "device": "fully ducted return and/or exhaust air systems", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "189.1-2014", + "device": "fully ducted return and/or exhaust air systems for laboratory and vivarium systems", + "adjustment_in_wc": 2.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "189.1-2014", + "device": "return and/or exhaust airflow control devices", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "189.1-2014", + "device": "exhaust filters, scrubbers, or other exhaust treatment", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "189.1-2014", + "device": "particulate filtration credit: merv 9 through 12", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "189.1-2014", + "device": "particulate filtration credit: merv 13 through 15", + "adjustment_in_wc": 0.9, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "189.1-2014", + "device": "particulate filtration credit: merv 16 and greater and electronically enhanced filters", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2, clean filter" + }, + { + "template": "189.1-2014", + "device": "carbon and other gas-phase air cleaners", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2, clean filter" + }, + { + "template": "189.1-2014", + "device": "biosafety cabinet", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "189.1-2014", + "device": "energy recovery device, other than coil runaround loop for each airstream", + "adjustment_in_wc": -0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": 2.2, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "189.1-2014", + "device": "coil runaround loop for each airstream", + "adjustment_in_wc": 0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "189.1-2014", + "device": "evaporative humidifier/cooler in series with another cooling coil", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "189.1-2014", + "device": "sound attenuation section", + "adjustment_in_wc": 0.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "189.1-2014", + "device": "exhaust system serving fume hoods", + "adjustment_in_wc": 0.35, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "189.1-2014", + "device": "laboratory and vivarium exhaust systems in high-rise buildings", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": 0.25, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "189.1-2014", + "device": "systems without central cooling device", + "adjustment_in_wc": -0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "189.1-2014", + "device": "systems without central heating device", + "adjustment_in_wc": -0.3, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "189.1-2014", + "device": "systems with central electric resistance heat", + "adjustment_in_wc": -0.2, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "189.1-2017", + "device": "fully ducted return and/or exhaust air systems", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "189.1-2017", + "device": "fully ducted return and/or exhaust air systems for laboratory and vivarium systems", + "adjustment_in_wc": 2.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "189.1-2017", + "device": "return and/or exhaust airflow control devices", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "189.1-2017", + "device": "exhaust filters, scrubbers, or other exhaust treatment", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "189.1-2017", + "device": "particulate filtration credit: merv 9 through 12", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "189.1-2017", + "device": "particulate filtration credit: merv 13 through 15", + "adjustment_in_wc": 0.9, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "189.1-2017", + "device": "particulate filtration credit: merv 16 and greater and electronically enhanced filters", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2, clean filter" + }, + { + "template": "189.1-2017", + "device": "carbon and other gas-phase air cleaners", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2, clean filter" + }, + { + "template": "189.1-2017", + "device": "biosafety cabinet", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "189.1-2017", + "device": "energy recovery device, other than coil runaround loop for each airstream", + "adjustment_in_wc": -0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": 2.2, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "189.1-2017", + "device": "coil runaround loop for each airstream", + "adjustment_in_wc": 0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "189.1-2017", + "device": "evaporative humidifier/cooler in series with another cooling coil", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "189.1-2017", + "device": "sound attenuation section", + "adjustment_in_wc": 0.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "189.1-2017", + "device": "exhaust system serving fume hoods", + "adjustment_in_wc": 0.35, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "189.1-2017", + "device": "laboratory and vivarium exhaust systems in high-rise buildings", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": 0.25, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "189.1-2017", + "device": "systems without central cooling device", + "adjustment_in_wc": -0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "189.1-2017", + "device": "systems without central heating device", + "adjustment_in_wc": -0.3, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "189.1-2017", + "device": "systems with central electric resistance heat", + "adjustment_in_wc": -0.2, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "189.1-2020", + "device": "fully ducted return and/or exhaust air systems", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2020", + "device": "fully ducted return and/or exhaust air systems for laboratory and vivarium systems", + "adjustment_in_wc": 2.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2020", + "device": "return and/or exhaust airflow control devices", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2020", + "device": "exhaust filters, scrubbers, or other exhaust treatment", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2020", + "device": "particulate filtration credit: merv 9 through 12", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2020", + "device": "particulate filtration credit: merv 13 through 15", + "adjustment_in_wc": 0.9, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2020", + "device": "particulate filtration credit: merv 16 and greater and electronically enhanced filters", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2, clean filter" + }, + { + "template": "189.1-2020", + "device": "carbon and other gas-phase air cleaners", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2, clean filter" + }, + { + "template": "189.1-2020", + "device": "biosafety cabinet", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2020", + "device": "energy recovery device, other than coil runaround loop for each airstream", + "adjustment_in_wc": -0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": 2.2, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2020", + "device": "coil runaround loop for each airstream", + "adjustment_in_wc": 0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2020", + "device": "evaporative humidifier/cooler in series with another cooling coil", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2020", + "device": "sound attenuation section", + "adjustment_in_wc": 0.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2020", + "device": "exhaust system serving fume hoods", + "adjustment_in_wc": 0.35, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2020", + "device": "laboratory and vivarium exhaust systems in high-rise buildings", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": 0.25, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2020", + "device": "systems without central cooling device", + "adjustment_in_wc": -0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2020", + "device": "systems without central heating device", + "adjustment_in_wc": -0.3, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2020", + "device": "systems with central electric resistance heat", + "adjustment_in_wc": -0.2, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2023", + "device": "fully ducted return and/or exhaust air systems", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2023", + "device": "fully ducted return and/or exhaust air systems for laboratory and vivarium systems", + "adjustment_in_wc": 2.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2023", + "device": "return and/or exhaust airflow control devices", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2023", + "device": "exhaust filters, scrubbers, or other exhaust treatment", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2023", + "device": "particulate filtration credit: merv 9 through 12", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2023", + "device": "particulate filtration credit: merv 13 through 15", + "adjustment_in_wc": 0.9, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2023", + "device": "particulate filtration credit: merv 16 and greater and electronically enhanced filters", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2, clean filter" + }, + { + "template": "189.1-2023", + "device": "carbon and other gas-phase air cleaners", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2, clean filter" + }, + { + "template": "189.1-2023", + "device": "biosafety cabinet", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2023", + "device": "energy recovery device, other than coil runaround loop for each airstream", + "adjustment_in_wc": -0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": 2.2, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2023", + "device": "coil runaround loop for each airstream", + "adjustment_in_wc": 0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2023", + "device": "evaporative humidifier/cooler in series with another cooling coil", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2023", + "device": "sound attenuation section", + "adjustment_in_wc": 0.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2023", + "device": "exhaust system serving fume hoods", + "adjustment_in_wc": 0.35, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2023", + "device": "laboratory and vivarium exhaust systems in high-rise buildings", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": 0.25, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2023", + "device": "systems without central cooling device", + "adjustment_in_wc": -0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2023", + "device": "systems without central heating device", + "adjustment_in_wc": -0.3, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "189.1-2023", + "device": "systems with central electric resistance heat", + "adjustment_in_wc": -0.2, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + } +] \ No newline at end of file diff --git a/building_energy_standards_data/database_files/system_requirements_fan_power_allowance_pressure_drop_adjustment_90_1.json b/building_energy_standards_data/database_files/system_requirements_fan_power_allowance_pressure_drop_adjustment_90_1.json new file mode 100644 index 0000000..c479f2e --- /dev/null +++ b/building_energy_standards_data/database_files/system_requirements_fan_power_allowance_pressure_drop_adjustment_90_1.json @@ -0,0 +1,982 @@ +[ + { + "template": "90.1-2007", + "device": "fully ducted return and/or exhaust air systems", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2007", + "device": "return and/or exhaust airflow control devices", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2007", + "device": "exhaust filters, scrubbers, or other exhaust treatment", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2007", + "device": "particulate filtration credit: merv 9 through 12", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2007", + "device": "particulate filtration credit: merv 13 through 15", + "adjustment_in_wc": 0.9, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2007", + "device": "particulate filtration credit: merv 16 and greater and electronically enhanced filters", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B, clean filter" + }, + { + "template": "90.1-2007", + "device": "carbon and other gas-phase air cleaners", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B, clean filter" + }, + { + "template": "90.1-2007", + "device": "heat recovery device", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2007", + "device": "evaporative humidifier/cooler in series with another cooling coil", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2007", + "device": "sound attenuation section", + "adjustment_in_wc": 0.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2007", + "device": "fume hood exhaust exception", + "adjustment_in_wc": -1, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2007, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2010", + "device": "fully ducted return and/or exhaust air systems", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2010", + "device": "fully ducted return and/or exhaust air systems for laboratory and vivarium systems", + "adjustment_in_wc": 2.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2010", + "device": "return and/or exhaust airflow control devices", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2010", + "device": "exhaust filters, scrubbers, or other exhaust treatment", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2010", + "device": "particulate filtration credit: merv 9 through 12", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2010", + "device": "particulate filtration credit: merv 13 through 15", + "adjustment_in_wc": 0.9, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2010", + "device": "particulate filtration credit: merv 16 and greater and electronically enhanced filters", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B, clean filter" + }, + { + "template": "90.1-2010", + "device": "carbon and other gas-phase air cleaners", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B, clean filter" + }, + { + "template": "90.1-2010", + "device": "biosafety cabinet", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2010", + "device": "energy recovery device, other than coil runaround loop for each airstream", + "adjustment_in_wc": -0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": 2.2, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2010", + "device": "coil runaround loop for each airstream", + "adjustment_in_wc": 0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2010", + "device": "evaporative humidifier/cooler in series with another cooling coil", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2010", + "device": "sound attenuation section", + "adjustment_in_wc": 0.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2010", + "device": "exhaust system serving fume hoods", + "adjustment_in_wc": 0.35, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2010", + "device": "laboratory and vivarium exhaust systems in high-rise buildings", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": 0.25, + "annotation": "From 90.1-2010, Table 6.5.3.1.1B" + }, + { + "template": "90.1-2013", + "device": "fully ducted return and/or exhaust air systems", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "90.1-2013", + "device": "fully ducted return and/or exhaust air systems for laboratory and vivarium systems", + "adjustment_in_wc": 2.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "90.1-2013", + "device": "return and/or exhaust airflow control devices", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "90.1-2013", + "device": "exhaust filters, scrubbers, or other exhaust treatment", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "90.1-2013", + "device": "particulate filtration credit: merv 9 through 12", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "90.1-2013", + "device": "particulate filtration credit: merv 13 through 15", + "adjustment_in_wc": 0.9, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "90.1-2013", + "device": "particulate filtration credit: merv 16 and greater and electronically enhanced filters", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2, clean filter" + }, + { + "template": "90.1-2013", + "device": "carbon and other gas-phase air cleaners", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2, clean filter" + }, + { + "template": "90.1-2013", + "device": "biosafety cabinet", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "90.1-2013", + "device": "energy recovery device, other than coil runaround loop for each airstream", + "adjustment_in_wc": -0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": 2.2, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "90.1-2013", + "device": "coil runaround loop for each airstream", + "adjustment_in_wc": 0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "90.1-2013", + "device": "evaporative humidifier/cooler in series with another cooling coil", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "90.1-2013", + "device": "sound attenuation section", + "adjustment_in_wc": 0.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "90.1-2013", + "device": "exhaust system serving fume hoods", + "adjustment_in_wc": 0.35, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "90.1-2013", + "device": "laboratory and vivarium exhaust systems in high-rise buildings", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": 0.25, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "90.1-2013", + "device": "systems without central cooling device", + "adjustment_in_wc": -0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "90.1-2013", + "device": "systems without central heating device", + "adjustment_in_wc": -0.3, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "90.1-2013", + "device": "systems with central electric resistance heat", + "adjustment_in_wc": -0.2, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2013, Table 6.5.3.1-2" + }, + { + "template": "90.1-2016", + "device": "fully ducted return and/or exhaust air systems", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "90.1-2016", + "device": "fully ducted return and/or exhaust air systems for laboratory and vivarium systems", + "adjustment_in_wc": 2.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "90.1-2016", + "device": "return and/or exhaust airflow control devices", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "90.1-2016", + "device": "exhaust filters, scrubbers, or other exhaust treatment", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "90.1-2016", + "device": "particulate filtration credit: merv 9 through 12", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "90.1-2016", + "device": "particulate filtration credit: merv 13 through 15", + "adjustment_in_wc": 0.9, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "90.1-2016", + "device": "particulate filtration credit: merv 16 and greater and electronically enhanced filters", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2, clean filter" + }, + { + "template": "90.1-2016", + "device": "carbon and other gas-phase air cleaners", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2, clean filter" + }, + { + "template": "90.1-2016", + "device": "biosafety cabinet", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "90.1-2016", + "device": "energy recovery device, other than coil runaround loop for each airstream", + "adjustment_in_wc": -0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": 2.2, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "90.1-2016", + "device": "coil runaround loop for each airstream", + "adjustment_in_wc": 0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "90.1-2016", + "device": "evaporative humidifier/cooler in series with another cooling coil", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "90.1-2016", + "device": "sound attenuation section", + "adjustment_in_wc": 0.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "90.1-2016", + "device": "exhaust system serving fume hoods", + "adjustment_in_wc": 0.35, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "90.1-2016", + "device": "laboratory and vivarium exhaust systems in high-rise buildings", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": 0.25, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "90.1-2016", + "device": "systems without central cooling device", + "adjustment_in_wc": -0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "90.1-2016", + "device": "systems without central heating device", + "adjustment_in_wc": -0.3, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "90.1-2016", + "device": "systems with central electric resistance heat", + "adjustment_in_wc": -0.2, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2016, Table 6.5.3.1-2" + }, + { + "template": "90.1-2019", + "device": "fully ducted return and/or exhaust air systems", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "90.1-2019", + "device": "fully ducted return and/or exhaust air systems for laboratory and vivarium systems", + "adjustment_in_wc": 2.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "90.1-2019", + "device": "return and/or exhaust airflow control devices", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "90.1-2019", + "device": "exhaust filters, scrubbers, or other exhaust treatment", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "90.1-2019", + "device": "particulate filtration credit: merv 9 through 12", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "90.1-2019", + "device": "particulate filtration credit: merv 13 through 15", + "adjustment_in_wc": 0.9, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "90.1-2019", + "device": "particulate filtration credit: merv 16 and greater and electronically enhanced filters", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2, clean filter" + }, + { + "template": "90.1-2019", + "device": "carbon and other gas-phase air cleaners", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2, clean filter" + }, + { + "template": "90.1-2019", + "device": "biosafety cabinet", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "90.1-2019", + "device": "energy recovery device, other than coil runaround loop for each airstream", + "adjustment_in_wc": -0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": 2.2, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "90.1-2019", + "device": "coil runaround loop for each airstream", + "adjustment_in_wc": 0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "90.1-2019", + "device": "evaporative humidifier/cooler in series with another cooling coil", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "90.1-2019", + "device": "sound attenuation section", + "adjustment_in_wc": 0.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "90.1-2019", + "device": "exhaust system serving fume hoods", + "adjustment_in_wc": 0.35, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "90.1-2019", + "device": "laboratory and vivarium exhaust systems in high-rise buildings", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": 0.25, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "90.1-2019", + "device": "systems without central cooling device", + "adjustment_in_wc": -0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "90.1-2019", + "device": "systems without central heating device", + "adjustment_in_wc": -0.3, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "90.1-2019", + "device": "systems with central electric resistance heat", + "adjustment_in_wc": -0.2, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2019, Table 6.5.3.1-2" + }, + { + "template": "90.1-2022", + "device": "fully ducted return and/or exhaust air systems", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2022, Table 6.5.3.1-2" + }, + { + "template": "90.1-2022", + "device": "fully ducted return and/or exhaust air systems for laboratory and vivarium systems", + "adjustment_in_wc": 2.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2022, Table 6.5.3.1-2" + }, + { + "template": "90.1-2022", + "device": "return and/or exhaust airflow control devices", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2022, Table 6.5.3.1-2" + }, + { + "template": "90.1-2022", + "device": "exhaust filters, scrubbers, or other exhaust treatment", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2022, Table 6.5.3.1-2" + }, + { + "template": "90.1-2022", + "device": "particulate filtration credit: merv 9 through 12", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2022, Table 6.5.3.1-2" + }, + { + "template": "90.1-2022", + "device": "particulate filtration credit: merv 13 through 15", + "adjustment_in_wc": 0.9, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2022, Table 6.5.3.1-2" + }, + { + "template": "90.1-2022", + "device": "particulate filtration credit: merv 16 and greater and electronically enhanced filters", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2022, Table 6.5.3.1-2, clean filter" + }, + { + "template": "90.1-2022", + "device": "carbon and other gas-phase air cleaners", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2022, Table 6.5.3.1-2, clean filter" + }, + { + "template": "90.1-2022", + "device": "biosafety cabinet", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2022, Table 6.5.3.1-2" + }, + { + "template": "90.1-2022", + "device": "energy recovery device, other than coil runaround loop for each airstream", + "adjustment_in_wc": -0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": 2.2, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2022, Table 6.5.3.1-2" + }, + { + "template": "90.1-2022", + "device": "coil runaround loop for each airstream", + "adjustment_in_wc": 0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2022, Table 6.5.3.1-2" + }, + { + "template": "90.1-2022", + "device": "evaporative humidifier/cooler in series with another cooling coil", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2022, Table 6.5.3.1-2" + }, + { + "template": "90.1-2022", + "device": "sound attenuation section", + "adjustment_in_wc": 0.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2022, Table 6.5.3.1-2" + }, + { + "template": "90.1-2022", + "device": "exhaust system serving fume hoods", + "adjustment_in_wc": 0.35, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2022, Table 6.5.3.1-2" + }, + { + "template": "90.1-2022", + "device": "laboratory and vivarium exhaust systems in high-rise buildings", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": 0.25, + "annotation": "From 90.1-2022, Table 6.5.3.1-2" + }, + { + "template": "90.1-2022", + "device": "systems without central cooling device", + "adjustment_in_wc": -0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2022, Table 6.5.3.1-2" + }, + { + "template": "90.1-2022", + "device": "systems without central heating device", + "adjustment_in_wc": -0.3, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2022, Table 6.5.3.1-2" + }, + { + "template": "90.1-2022", + "device": "systems with central electric resistance heat", + "adjustment_in_wc": -0.2, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From 90.1-2022, Table 6.5.3.1-2" + } +] \ No newline at end of file diff --git a/building_energy_standards_data/database_files/system_requirements_fan_power_allowance_pressure_drop_adjustment_IECC.json b/building_energy_standards_data/database_files/system_requirements_fan_power_allowance_pressure_drop_adjustment_IECC.json new file mode 100644 index 0000000..20fa533 --- /dev/null +++ b/building_energy_standards_data/database_files/system_requirements_fan_power_allowance_pressure_drop_adjustment_IECC.json @@ -0,0 +1,982 @@ +[ + { + "template": "IECC-2009", + "device": "fully ducted return and/or exhaust air systems", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2009, Table 503.2.10.1(2)" + }, + { + "template": "IECC-2009", + "device": "return and/or exhaust airflow control devices", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2009, Table 503.2.10.1(2)" + }, + { + "template": "IECC-2009", + "device": "exhaust filters, scrubbers, or other exhaust treatment", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2009, Table 503.2.10.1(2)" + }, + { + "template": "IECC-2009", + "device": "particulate filtration credit: merv 9 through 12", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2009, Table 503.2.10.1(2)" + }, + { + "template": "IECC-2009", + "device": "particulate filtration credit: merv 13 through 15", + "adjustment_in_wc": 0.9, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2009, Table 503.2.10.1(2)" + }, + { + "template": "IECC-2009", + "device": "particulate filtration credit: merv 16 and greater and electronically enhanced filters", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2009, Table 503.2.10.1(2), clean filter" + }, + { + "template": "IECC-2009", + "device": "carbon and other gas-phase air cleaners", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2009, Table 503.2.10.1(2), clean filter" + }, + { + "template": "IECC-2009", + "device": "heat recovery device", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2009, Table 503.2.10.1(2)" + }, + { + "template": "IECC-2009", + "device": "evaporative humidifier/cooler in series with another cooling coil", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2009, Table 503.2.10.1(2)" + }, + { + "template": "IECC-2009", + "device": "sound attenuation section", + "adjustment_in_wc": 0.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2009, Table 503.2.10.1(2)" + }, + { + "template": "IECC-2009", + "device": "fume hood exhaust exception", + "adjustment_in_wc": -1, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2009, Table 503.2.10.1(2)" + }, + { + "template": "IECC-2012", + "device": "fully ducted return and/or exhaust air systems", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2012, Table C403.2.10.1(2)" + }, + { + "template": "IECC-2012", + "device": "fully ducted return and/or exhaust air systems for laboratory and vivarium systems", + "adjustment_in_wc": 2.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2012, Table C403.2.10.1(2)" + }, + { + "template": "IECC-2012", + "device": "return and/or exhaust airflow control devices", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2012, Table C403.2.10.1(2)" + }, + { + "template": "IECC-2012", + "device": "exhaust filters, scrubbers, or other exhaust treatment", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2012, Table C403.2.10.1(2)" + }, + { + "template": "IECC-2012", + "device": "particulate filtration credit: merv 9 through 12", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2012, Table C403.2.10.1(2)" + }, + { + "template": "IECC-2012", + "device": "particulate filtration credit: merv 13 through 15", + "adjustment_in_wc": 0.9, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2012, Table C403.2.10.1(2)" + }, + { + "template": "IECC-2012", + "device": "particulate filtration credit: merv 16 and greater and electronically enhanced filters", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2012, Table C403.2.10.1(2), clean filter" + }, + { + "template": "IECC-2012", + "device": "carbon and other gas-phase air cleaners", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2012, Table C403.2.10.1(2), clean filter" + }, + { + "template": "IECC-2012", + "device": "biosafety cabinet", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2012, Table C403.2.10.1(2)" + }, + { + "template": "IECC-2012", + "device": "energy recovery device, other than coil runaround loop for each airstream", + "adjustment_in_wc": -0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": 2.2, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2012, Table C403.2.10.1(2)" + }, + { + "template": "IECC-2012", + "device": "coil runaround loop for each airstream", + "adjustment_in_wc": 0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2012, Table C403.2.10.1(2)" + }, + { + "template": "IECC-2012", + "device": "evaporative humidifier/cooler in series with another cooling coil", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2012, Table C403.2.10.1(2)" + }, + { + "template": "IECC-2012", + "device": "sound attenuation section", + "adjustment_in_wc": 0.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2012, Table C403.2.10.1(2)" + }, + { + "template": "IECC-2012", + "device": "exhaust system serving fume hoods", + "adjustment_in_wc": 0.35, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2012, Table C403.2.10.1(2)" + }, + { + "template": "IECC-2012", + "device": "laboratory and vivarium exhaust systems in high-rise buildings", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": 0.25, + "annotation": "From IECC-2012, Table C403.2.10.1(2)" + }, + { + "template": "IECC-2015", + "device": "fully ducted return and/or exhaust air systems", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2015, Table C403.2.12.1(2)" + }, + { + "template": "IECC-2015", + "device": "fully ducted return and/or exhaust air systems for laboratory and vivarium systems", + "adjustment_in_wc": 2.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2015, Table C403.2.12.1(2)" + }, + { + "template": "IECC-2015", + "device": "return and/or exhaust airflow control devices", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2015, Table C403.2.12.1(2)" + }, + { + "template": "IECC-2015", + "device": "exhaust filters, scrubbers, or other exhaust treatment", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2015, Table C403.2.12.1(2)" + }, + { + "template": "IECC-2015", + "device": "particulate filtration credit: merv 9 through 12", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2015, Table C403.2.12.1(2)" + }, + { + "template": "IECC-2015", + "device": "particulate filtration credit: merv 13 through 15", + "adjustment_in_wc": 0.9, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2015, Table C403.2.12.1(2)" + }, + { + "template": "IECC-2015", + "device": "particulate filtration credit: merv 16 and greater and electronically enhanced filters", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2015, Table C403.2.12.1(2), clean filter" + }, + { + "template": "IECC-2015", + "device": "carbon and other gas-phase air cleaners", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2015, Table C403.2.12.1(2), clean filter" + }, + { + "template": "IECC-2015", + "device": "biosafety cabinet", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2015, Table C403.2.12.1(2)" + }, + { + "template": "IECC-2015", + "device": "energy recovery device, other than coil runaround loop for each airstream", + "adjustment_in_wc": -0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": 2.2, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2015, Table C403.2.12.1(2)" + }, + { + "template": "IECC-2015", + "device": "coil runaround loop for each airstream", + "adjustment_in_wc": 0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2015, Table C403.2.12.1(2)" + }, + { + "template": "IECC-2015", + "device": "evaporative humidifier/cooler in series with another cooling coil", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2015, Table C403.2.12.1(2)" + }, + { + "template": "IECC-2015", + "device": "sound attenuation section", + "adjustment_in_wc": 0.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2015, Table C403.2.12.1(2)" + }, + { + "template": "IECC-2015", + "device": "exhaust system serving fume hoods", + "adjustment_in_wc": 0.35, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2015, Table C403.2.12.1(2)" + }, + { + "template": "IECC-2015", + "device": "laboratory and vivarium exhaust systems in high-rise buildings", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": 0.25, + "annotation": "From IECC-2015, Table C403.2.12.1(2)" + }, + { + "template": "IECC-2015", + "device": "systems without central cooling device", + "adjustment_in_wc": -0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2015, Table C403.2.12.1(2)" + }, + { + "template": "IECC-2015", + "device": "systems without central heating device", + "adjustment_in_wc": -0.3, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2015, Table C403.2.12.1(2)" + }, + { + "template": "IECC-2015", + "device": "systems with central electric resistance heat", + "adjustment_in_wc": -0.2, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2015, Table C403.2.12.1(2)" + }, + { + "template": "IECC-2018", + "device": "fully ducted return and/or exhaust air systems", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2018, Table C403.8.1(2)" + }, + { + "template": "IECC-2018", + "device": "fully ducted return and/or exhaust air systems for laboratory and vivarium systems", + "adjustment_in_wc": 2.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2018, Table C403.8.1(2)" + }, + { + "template": "IECC-2018", + "device": "return and/or exhaust airflow control devices", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2018, Table C403.8.1(2)" + }, + { + "template": "IECC-2018", + "device": "exhaust filters, scrubbers, or other exhaust treatment", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2018, Table C403.8.1(2)" + }, + { + "template": "IECC-2018", + "device": "particulate filtration credit: merv 9 through 12", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2018, Table C403.8.1(2)" + }, + { + "template": "IECC-2018", + "device": "particulate filtration credit: merv 13 through 15", + "adjustment_in_wc": 0.9, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2018, Table C403.8.1(2)" + }, + { + "template": "IECC-2018", + "device": "particulate filtration credit: merv 16 and greater and electronically enhanced filters", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2018, Table C403.8.1(2), clean filter" + }, + { + "template": "IECC-2018", + "device": "carbon and other gas-phase air cleaners", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2018, Table C403.8.1(2), clean filter" + }, + { + "template": "IECC-2018", + "device": "biosafety cabinet", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2018, Table C403.8.1(2)" + }, + { + "template": "IECC-2018", + "device": "energy recovery device, other than coil runaround loop for each airstream", + "adjustment_in_wc": -0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": 2.2, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2018, Table C403.8.1(2)" + }, + { + "template": "IECC-2018", + "device": "coil runaround loop for each airstream", + "adjustment_in_wc": 0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2018, Table C403.8.1(2)" + }, + { + "template": "IECC-2018", + "device": "evaporative humidifier/cooler in series with another cooling coil", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2018, Table C403.8.1(2)" + }, + { + "template": "IECC-2018", + "device": "sound attenuation section", + "adjustment_in_wc": 0.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2018, Table C403.8.1(2)" + }, + { + "template": "IECC-2018", + "device": "exhaust system serving fume hoods", + "adjustment_in_wc": 0.35, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2018, Table C403.8.1(2)" + }, + { + "template": "IECC-2018", + "device": "laboratory and vivarium exhaust systems in high-rise buildings", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": 0.25, + "annotation": "From IECC-2018, Table C403.8.1(2)" + }, + { + "template": "IECC-2018", + "device": "systems without central cooling device", + "adjustment_in_wc": -0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2018, Table C403.8.1(2)" + }, + { + "template": "IECC-2018", + "device": "systems without central heating device", + "adjustment_in_wc": -0.3, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2018, Table C403.8.1(2)" + }, + { + "template": "IECC-2018", + "device": "systems with central electric resistance heat", + "adjustment_in_wc": -0.2, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2018, Table C403.8.1(2)" + }, + { + "template": "IECC-2021", + "device": "fully ducted return and/or exhaust air systems", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2021, Table C403.8.1(2)" + }, + { + "template": "IECC-2021", + "device": "fully ducted return and/or exhaust air systems for laboratory and vivarium systems", + "adjustment_in_wc": 2.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2021, Table C403.8.1(2)" + }, + { + "template": "IECC-2021", + "device": "return and/or exhaust airflow control devices", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2021, Table C403.8.1(2)" + }, + { + "template": "IECC-2021", + "device": "exhaust filters, scrubbers, or other exhaust treatment", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2021, Table C403.8.1(2)" + }, + { + "template": "IECC-2021", + "device": "particulate filtration credit: merv 9 through 12", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2021, Table C403.8.1(2)" + }, + { + "template": "IECC-2021", + "device": "particulate filtration credit: merv 13 through 15", + "adjustment_in_wc": 0.9, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2021, Table C403.8.1(2)" + }, + { + "template": "IECC-2021", + "device": "particulate filtration credit: merv 16 and greater and electronically enhanced filters", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2021, Table C403.8.1(2), clean filter" + }, + { + "template": "IECC-2021", + "device": "carbon and other gas-phase air cleaners", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2021, Table C403.8.1(2), clean filter" + }, + { + "template": "IECC-2021", + "device": "biosafety cabinet", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2021, Table C403.8.1(2)" + }, + { + "template": "IECC-2021", + "device": "energy recovery device, other than coil runaround loop for each airstream", + "adjustment_in_wc": -0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": 2.2, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2021, Table C403.8.1(2)" + }, + { + "template": "IECC-2021", + "device": "coil runaround loop for each airstream", + "adjustment_in_wc": 0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2021, Table C403.8.1(2)" + }, + { + "template": "IECC-2021", + "device": "evaporative humidifier/cooler in series with another cooling coil", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2021, Table C403.8.1(2)" + }, + { + "template": "IECC-2021", + "device": "sound attenuation section", + "adjustment_in_wc": 0.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2021, Table C403.8.1(2)" + }, + { + "template": "IECC-2021", + "device": "exhaust system serving fume hoods", + "adjustment_in_wc": 0.35, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2021, Table C403.8.1(2)" + }, + { + "template": "IECC-2021", + "device": "laboratory and vivarium exhaust systems in high-rise buildings", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": 0.25, + "annotation": "From IECC-2021, Table C403.8.1(2)" + }, + { + "template": "IECC-2021", + "device": "systems without central cooling device", + "adjustment_in_wc": -0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2021, Table C403.8.1(2)" + }, + { + "template": "IECC-2021", + "device": "systems without central heating device", + "adjustment_in_wc": -0.3, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2021, Table C403.8.1(2)" + }, + { + "template": "IECC-2021", + "device": "systems with central electric resistance heat", + "adjustment_in_wc": -0.2, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2021, Table C403.8.1(2)" + }, + { + "template": "IECC-2024", + "device": "fully ducted return and/or exhaust air systems", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2024, Table C403.8.1(2)" + }, + { + "template": "IECC-2024", + "device": "fully ducted return and/or exhaust air systems for laboratory and vivarium systems", + "adjustment_in_wc": 2.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2024, Table C403.8.1(2)" + }, + { + "template": "IECC-2024", + "device": "return and/or exhaust airflow control devices", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2024, Table C403.8.1(2)" + }, + { + "template": "IECC-2024", + "device": "exhaust filters, scrubbers, or other exhaust treatment", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2024, Table C403.8.1(2)" + }, + { + "template": "IECC-2024", + "device": "particulate filtration credit: merv 9 through 12", + "adjustment_in_wc": 0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2024, Table C403.8.1(2)" + }, + { + "template": "IECC-2024", + "device": "particulate filtration credit: merv 13 through 15", + "adjustment_in_wc": 0.9, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2024, Table C403.8.1(2)" + }, + { + "template": "IECC-2024", + "device": "particulate filtration credit: merv 16 and greater and electronically enhanced filters", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2024, Table C403.8.1(2), clean filter" + }, + { + "template": "IECC-2024", + "device": "carbon and other gas-phase air cleaners", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2024, Table C403.8.1(2), clean filter" + }, + { + "template": "IECC-2024", + "device": "biosafety cabinet", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2024, Table C403.8.1(2)" + }, + { + "template": "IECC-2024", + "device": "energy recovery device, other than coil runaround loop for each airstream", + "adjustment_in_wc": -0.5, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": 2.2, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2024, Table C403.8.1(2)" + }, + { + "template": "IECC-2024", + "device": "coil runaround loop for each airstream", + "adjustment_in_wc": 0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2024, Table C403.8.1(2)" + }, + { + "template": "IECC-2024", + "device": "evaporative humidifier/cooler in series with another cooling coil", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": "TRUE", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2024, Table C403.8.1(2)" + }, + { + "template": "IECC-2024", + "device": "sound attenuation section", + "adjustment_in_wc": 0.15, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2024, Table C403.8.1(2)" + }, + { + "template": "IECC-2024", + "device": "exhaust system serving fume hoods", + "adjustment_in_wc": 0.35, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2024, Table C403.8.1(2)" + }, + { + "template": "IECC-2024", + "device": "laboratory and vivarium exhaust systems in high-rise buildings", + "adjustment_in_wc": null, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": 0.25, + "annotation": "From IECC-2024, Table C403.8.1(2)" + }, + { + "template": "IECC-2024", + "device": "systems without central cooling device", + "adjustment_in_wc": -0.6, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2024, Table C403.8.1(2)" + }, + { + "template": "IECC-2024", + "device": "systems without central heating device", + "adjustment_in_wc": -0.3, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2024, Table C403.8.1(2)" + }, + { + "template": "IECC-2024", + "device": "systems with central electric resistance heat", + "adjustment_in_wc": -0.2, + "adjustment_in_wc_at_fan_system_design_conditions": null, + "adjustment_in_wc_2_times_at_fan_system_design_conditions": null, + "adjustment_in_wc_effectiveness_multiplier": null, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": null, + "annotation": "From IECC-2024, Table C403.8.1(2)" + } +] \ No newline at end of file diff --git a/building_energy_standards_data/database_tables/__init__.py b/building_energy_standards_data/database_tables/__init__.py index 6a7d889..b6655c2 100644 --- a/building_energy_standards_data/database_tables/__init__.py +++ b/building_energy_standards_data/database_tables/__init__.py @@ -132,6 +132,9 @@ "system_requirements_fan_power_allowance_90_1", "system_requirements_fan_power_allowance_IECC", "system_requirements_fan_power_allowance_189_1", + "system_requirements_fan_power_allowance_pressure_drop_adjustment_90_1", + "system_requirements_fan_power_allowance_pressure_drop_adjustment_IECC", + "system_requirements_fan_power_allowance_pressure_drop_adjustment_189_1", "system_requirements_fan_power_allowance_altitude_correction_factor_90_1", "system_requirements_heat_rejection_90_1", "system_requirements_heat_rejection_189_1", diff --git a/building_energy_standards_data/database_tables/system_requirements_fan_power_allowance_pressure_drop_adjustment.py b/building_energy_standards_data/database_tables/system_requirements_fan_power_allowance_pressure_drop_adjustment.py new file mode 100644 index 0000000..f2bf19f --- /dev/null +++ b/building_energy_standards_data/database_tables/system_requirements_fan_power_allowance_pressure_drop_adjustment.py @@ -0,0 +1,123 @@ +from building_energy_standards_data.database_engine.database import DBOperation +from building_energy_standards_data.database_engine.database_util import ( + is_float, + getattr_either, +) + +RECORD_HELP = """ +Must provide a tuple that contains: +template: TEXT +device: TEXT +adjustment_in_wc: NUMERIC +adjustment_in_wc_at_fan_system_design_conditions: TEXT +adjustment_in_wc_2_times_at_fan_system_design_conditions: TEXT +adjustment_in_wc_effectiveness_multiplier: NUMERIC +adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft: NUMERIC +annotation: TEXT (optional) +""" + +CREATE_SYSTEM_requirements_fan_power_allowance_pressure_drop_adjustment_TABLE = """ +CREATE TABLE IF NOT EXISTS %s +(id INTEGER PRIMARY KEY, +template TEXT NOT NULL, +device TEXT, +adjustment_in_wc NUMERIC, +adjustment_in_wc_at_fan_system_design_conditions TEXT, +adjustment_in_wc_2_times_at_fan_system_design_conditions TEXT, +adjustment_in_wc_effectiveness_multiplier NUMERIC, +adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft NUMERIC, +annotation TEXT); +""" + +INSERT_A_SYSTEM_requirements_fan_power_allowance_pressure_drop_adjustment_RECORD = """ + INSERT INTO %s ( +template, +device, +adjustment_in_wc, +adjustment_in_wc_at_fan_system_design_conditions, +adjustment_in_wc_2_times_at_fan_system_design_conditions, +adjustment_in_wc_effectiveness_multiplier, +adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft, +annotation +) +VALUES (?, ?, ?, ?, ?, ?, ?, ?); +""" + +RECORD_TEMPLATE = { + "template": "", + "device": "", + "adjustment_in_wc": 0.0, + "adjustment_in_wc_at_fan_system_design_conditions": "", + "adjustment_in_wc_2_times_at_fan_system_design_conditions": "", + "adjustment_in_wc_effectiveness_multiplier": 0.0, + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft": 0.0, + "annotation": "", +} + + +class SystemRequirementsFanPowerAllowancePressureDropAdjustment(DBOperation): + def __init__(self, table_name, initial_data_directory): + super(SystemRequirementsFanPowerAllowancePressureDropAdjustment, self).__init__( + table_name=table_name, + record_template=RECORD_TEMPLATE, + initial_data_directory=initial_data_directory, + create_table_query=CREATE_SYSTEM_requirements_fan_power_allowance_pressure_drop_adjustment_TABLE + % table_name, + insert_record_query=INSERT_A_SYSTEM_requirements_fan_power_allowance_pressure_drop_adjustment_RECORD + % table_name, + ) + + def get_record_info(self): + """ + A function to return the record info of the table + :return: + """ + return RECORD_HELP + + def validate_record_datatype(self, record): + str_expected = [ + "template", + "device" "adjustment_in_wc_at_fan_system_design_conditions", + "adjustment_in_wc_2_times_at_fan_system_design_conditions", + ] + + for f in str_expected: + if record.get(f): + assert isinstance( + record[f], str + ), f"{f} requires to be a string, instead got {record[f]}" + + float_expected = [ + "adjustment_in_wc", + "adjustment_in_wc_effectiveness_multiplier", + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft", + ] + + for f in float_expected: + if record.get(f): + assert is_float( + record.get(f) + ), f"{f} requires to be numeric data type, instead got {record[f]}" + return True + + def _preprocess_record(self, record): + """ + + :param record: dict + :return: + """ + + return ( + getattr_either("template", record), + getattr_either("device", record), + getattr_either("adjustment_in_wc", record), + getattr_either("adjustment_in_wc_at_fan_system_design_conditions", record), + getattr_either( + "adjustment_in_wc_2_times_at_fan_system_design_conditions", record + ), + getattr_either("adjustment_in_wc_effectiveness_multiplier", record), + getattr_either( + "adjustment_in_wc_per_100_ft_of_verticaul_duct_exceeding_75_ft", record + ), + getattr_either("annotation", record), + ) diff --git a/building_energy_standards_data/database_tables/system_requirements_fan_power_allowance_pressure_drop_adjustment_189_1.py b/building_energy_standards_data/database_tables/system_requirements_fan_power_allowance_pressure_drop_adjustment_189_1.py new file mode 100644 index 0000000..c0e5d9c --- /dev/null +++ b/building_energy_standards_data/database_tables/system_requirements_fan_power_allowance_pressure_drop_adjustment_189_1.py @@ -0,0 +1,19 @@ +import sqlite3 + +from building_energy_standards_data.database_tables.system_requirements_fan_power_allowance_pressure_drop_adjustment import ( + SystemRequirementsFanPowerAllowancePressureDropAdjustment, +) + +TABLE_NAME = "system_requirements_fan_power_allowance_pressure_drop_adjustment_189_1" + + +class SystemRequirementsFanPowerAllowancePressureDropAdjustment1891Table( + SystemRequirementsFanPowerAllowancePressureDropAdjustment +): + def __init__(self): + super( + SystemRequirementsFanPowerAllowancePressureDropAdjustment1891Table, self + ).__init__( + table_name=TABLE_NAME, + initial_data_directory=f"building_energy_standards_data/database_files/{TABLE_NAME}", + ) diff --git a/building_energy_standards_data/database_tables/system_requirements_fan_power_allowance_pressure_drop_adjustment_90_1.py b/building_energy_standards_data/database_tables/system_requirements_fan_power_allowance_pressure_drop_adjustment_90_1.py new file mode 100644 index 0000000..a0eb5d0 --- /dev/null +++ b/building_energy_standards_data/database_tables/system_requirements_fan_power_allowance_pressure_drop_adjustment_90_1.py @@ -0,0 +1,19 @@ +import sqlite3 + +from building_energy_standards_data.database_tables.system_requirements_fan_power_allowance_pressure_drop_adjustment import ( + SystemRequirementsFanPowerAllowancePressureDropAdjustment, +) + +TABLE_NAME = "system_requirements_fan_power_allowance_pressure_drop_adjustment_90_1" + + +class SystemRequirementsFanPowerAllowancePressureDropAdjustment901Table( + SystemRequirementsFanPowerAllowancePressureDropAdjustment +): + def __init__(self): + super( + SystemRequirementsFanPowerAllowancePressureDropAdjustment901Table, self + ).__init__( + table_name=TABLE_NAME, + initial_data_directory=f"building_energy_standards_data/database_files/{TABLE_NAME}", + ) diff --git a/building_energy_standards_data/database_tables/system_requirements_fan_power_allowance_pressure_drop_adjustment_IECC.py b/building_energy_standards_data/database_tables/system_requirements_fan_power_allowance_pressure_drop_adjustment_IECC.py new file mode 100644 index 0000000..2bfe8d4 --- /dev/null +++ b/building_energy_standards_data/database_tables/system_requirements_fan_power_allowance_pressure_drop_adjustment_IECC.py @@ -0,0 +1,19 @@ +import sqlite3 + +from building_energy_standards_data.database_tables.system_requirements_fan_power_allowance_pressure_drop_adjustment import ( + SystemRequirementsFanPowerAllowancePressureDropAdjustment, +) + +TABLE_NAME = "system_requirements_fan_power_allowance_pressure_drop_adjustment_IECC" + + +class SystemRequirementsFanPowerAllowancePressureDropAdjustmentIECCTable( + SystemRequirementsFanPowerAllowancePressureDropAdjustment +): + def __init__(self): + super( + SystemRequirementsFanPowerAllowancePressureDropAdjustmentIECCTable, self + ).__init__( + table_name=TABLE_NAME, + initial_data_directory=f"building_energy_standards_data/database_files/{TABLE_NAME}", + )