The PID (Proportional-Integral-Derivative) controller is a widely used feedback controller. This class implements a generic structure that can be used to create a wide range of PID controllers. It can function independently or be subclassed to provide more specific controls based on a particular control loop. Integral retention on reset is supported, which prevents re-winding the integrator after temporary disabling in presence of constant disturbances.
The standard PID equation is given by:
command = pterm + iterm + dterm
where:
- pterm = pgain * error
- iterm = iterm + igain * error * dt
- dterm = dgain * derror
and:
- error = desired_state - measured_state
- derror = (error - errorlast) / dt
p(Proportional gain): This gain determines the reaction to the current error. A larger proportional gain results in a larger change in the controller output for a given change in the error.i(Integral gain): This gain determines the reaction based on the sum of recent errors. The integral term accounts for past values of the error and integrates them over time to produce thei_term. This helps in eliminating steady-state errors.d(Derivative gain): This gain determines the reaction based on the rate at which the error has been changing. The derivative term predicts future errors based on the rate of change of the current error. This helps in reducing overshoot, settling time, and other transient performance variables.u_clamp(Minimum and maximum bounds for the controller output): These bounds are applied to the final command output of the controller, ensuring the output stays within acceptable physical limits.tracking_time_constant(Tracking time constant): This parameter is specific to the 'back_calculation' anti-windup strategy. If set to 0.0 when this strategy is selected, a recommended default value will be applied.antiwindup_strat(Anti-windup strategy): This parameter selects how the integrator is prevented from winding up when the controller output saturates. Available options are:NONE: no anti-windup technique; the integral term accumulates without correction.BACK_CALCULATION: adjusts the integral term based on the difference between the unsaturated and saturated outputs using the tracking time constanttracking_time_constant. Faster correction for smallertracking_time_constant.CONDITIONAL_INTEGRATION: only updates the integral term when the controller is not in saturation or when the error drives the output away from saturation, freezing integration otherwise.
Anti-windup functionality is crucial for PID controllers, especially when the control output is subject to saturation (clamping). Without anti-windup, the integral term can accumulate excessively when the controller output is saturated, leading to large overshoots and sluggish response once the error changes direction. The control_toolbox::Pid class offers two anti-windup strategies:
-
BACK_CALCULATION: This strategy adjusts the integral term based on the difference between the saturated and unsaturated controller output. When the controller outputcommandexceeds the output limits (u_maxoru_min), the integral termi_termis adjusted by subtracting a value proportional to the difference between the saturated outputcommand_satand the unsaturated outputcommand. This prevents the integral term from accumulating beyond what is necessary to maintain the output at its saturation limit. Thetracking_time_constantparameter is used to tune the speed of this adjustment. A smaller value results in faster anti-windup action.The update rule for the integral term with back-calculation is:
iterm += dt * (igain * error + (1 / trktc) * (commandsat - command))
If
trk_tc, i.e.,tracking_time_constantparameter, is set to 0.0, a default value is calculated based on the proportional and derivative gains:- If
d_gainis not zero: trktc = √(dgain / igain) - If
d_gainis zero: trktc = pgain / igain
- If
-
CONDITIONAL_INTEGRATION: In this strategy, the integral term is only updated when the controller is not in saturation or when the error has a sign that would lead the controller out of saturation. Specifically, the integral term is frozen (not updated) if the controller output is saturated and the error has the same sign as the saturated output. This prevents further accumulation of the integral term in the direction of saturation.The integral term is updated only if the following condition is met:
(command - commandsat = 0) ∨ (error * command ≤ 0)
This means the integral term
i_termis updated asi_term += dt * i_gain * erroronly when the controller is not saturated, or when it is saturated but the error is driving the output away from the saturation limit.
To use the Pid class, you should first call some version of initialize() and then call compute_command() at every update step. For example:
control_toolbox::Pid pid;
pid.initialize(6.0, 1.0, 2.0, 5, -5,2,control_toolbox::AntiwindupStrategy::BACK_CALCULATION);
double position_desired = 0.5;
...
rclcpp::Time last_time = get_clock()->now();
while (true) {
rclcpp::Time time = get_clock()->now();
double effort = pid.compute_command(position_desired - currentPosition(), time - last_time);
last_time = time;
}- Visioli, A. Practical PID Control. London: Springer-Verlag London Limited, 2006. 476 p.
- Vrancic, D., Horowitz, R., & Hagiwara, T. “Antiwindup, Bumpless, and Conditioned Transfer Techniques for PID Controllers.” IEEE Control Systems Magazine, vol. 16, no. 4, 1996, pp. 48–57.
- Bohn, C.; Atherton, D. “An analysis package comparing PID anti-windup strategies.” IEEE Control Systems Magazine, 1995, pp. 34–40.
- Åström, K.; Hägglund, T. PID Controllers: Theory, Design and Tuning. Research Triangle Park, USA: ISA Press / Springer-Verlag London Limited, 1995. 343 p.