Wiseway UPS - Monitored OIDs

Overview

This document lists the SNMP OIDs monitored by the CheckMK plugin for Wiseway UPS devices. The plugin supports both standard RFC 1628 UPS MIB OIDs and enterprise-specific OIDs from vendor 44782.

Implemented OIDs by Service

System Information Service

Shows static UPS system information and configuration.

OID Description Example Value Unit
.1.3.6.1.2.1.33.1.1.2.0 upsIdentModel "6000VA" -
.1.3.6.1.2.1.33.1.1.3.0 upsIdentUPSSoftwareVersion "VER 6.xxx" -
.1.3.6.1.2.1.33.1.1.4.0 upsIdentAgentSoftwareVersion "2.0.0" -
.1.3.6.1.4.1.44782.1.4.4.1.2.0 ups1equipmentManufacturer "Others" -
.1.3.6.1.4.1.44782.1.4.1.5.0 systemSerialNumber "5A1903026810Q9100039" -
.1.3.6.1.4.1.44782.1.4.4.1.6.0 ups1installationTime "2020-06-13" -
.1.3.6.1.4.1.44782.1.4.4.1.8.0 ups1maintenanceExpirationTime "2022-06-13" -
.1.3.6.1.4.1.44782.1.4.4.1.9.0 ups1batteryInstallationReplacementTime "2021-06-13" -
.1.3.6.1.4.1.44782.1.4.4.1.10.0 ups1nextMaintenanceTimeOfBattery "2025-06-13" -
.1.3.6.1.4.1.44782.1.4.4.1.11.0 ups1ratedPower 5000 W
.1.3.6.1.4.1.44782.1.4.4.1.12.0 ups1ratedCapacityOfBattery 100 Ah
.1.3.6.1.4.1.44782.1.4.4.1.14.0 ups1numberOfBatteries 1 -
.1.3.6.1.4.1.44782.1.4.4.1.15.0 ups1numberOfBatteriesInASingleGroup 16 -

Battery Status Service

Monitors battery health, charge level, and runtime.

OID Description Example Value Unit Thresholds
.1.3.6.1.2.1.33.1.2.1.0 upsBatteryStatus 2 (batteryNormal) - -
.1.3.6.1.2.1.33.1.2.2.0 upsSecondsOnBattery 0 seconds -
.1.3.6.1.4.1.44782.1.4.4.1.16.0 ups1batteryStatus (enterprise) 2 - -
.1.3.6.1.4.1.44782.1.4.4.1.17.0 ups1batteryTimeRemaining 15 minutes → seconds WARN: 600s, CRIT: 300s
.1.3.6.1.4.1.44782.1.4.4.1.18.0 ups1remainingCapacityOfBattery 100 % WARN: 20%, CRIT: 10%
.1.3.6.1.4.1.44782.1.4.4.1.72.0 ups1batteryAbnormal 0 flag -
.1.3.6.1.4.1.44782.1.4.4.1.73.0 ups1batteryPowered 0 flag -
.1.3.6.1.4.1.44782.1.4.4.1.74.0 ups1batteryLowVoltage 0 flag -

Power Status Service

Monitors power source, operational mode, and power failures.

OID Description Example Value Unit
.1.3.6.1.2.1.33.1.4.1.0 upsOutputSource 3 (normal) -
.1.3.6.1.4.1.44782.1.4.4.1.39.0 ups1powerSupplyMode 2 (online) -
.1.3.6.1.4.1.935.1.1.1.4.1.1.0 upsBaseOutputStatus 2 (onLine) -
.1.3.6.1.2.1.33.1.3.1.0 upsInputLineBads 0 count
.1.3.6.1.4.1.44782.1.4.4.1.77.0 ups1inputAbnormal 0 flag
.1.3.6.1.4.1.44782.1.4.4.1.78.0 ups1outputAbnormal 0 flag
.1.3.6.1.4.1.44782.1.4.4.1.80.0 ups1bypassStatus 1 flag

Alarm Status Service

Monitors system alarms and critical conditions.

OID Description Example Value Unit
.1.3.6.1.4.1.44782.1.4.4.1.71.0 ups1abnormalCommunication 0 flag
.1.3.6.1.4.1.44782.1.4.4.1.76.0 ups1temperatureAbnormal 0 flag
.1.3.6.1.4.1.44782.1.4.4.1.79.0 ups1overLoad 0 flag
.1.3.6.1.4.1.44782.1.4.4.1.81.0 ups1fanFailure 0 flag
.1.3.6.1.4.1.44782.1.4.4.1.85.0 ups1shutdownRequest 0 flag
.1.3.6.1.4.1.44782.1.4.4.1.86.0 ups1testInProgress 1 flag
.1.3.6.1.4.1.44782.1.4.4.1.89.0 ups1shutdownImminent 0 flag
.1.3.6.1.4.1.44782.1.4.4.1.93.0 ups1lowBatteryShutdownImminent 0 flag
.1.3.6.1.4.1.44782.1.4.4.1.94.0 ups1systemStatus 1 status

Physical Measurement Services

Input Voltage Service

OID Description Example Value Unit Thresholds
.1.3.6.1.4.1.44782.1.4.4.1.27.0 ups1inputUPhaseVoltage 231.9 V WARN: 250V/210V, CRIT: 260V/200V

Output Voltage Service

OID Description Example Value Unit Thresholds
.1.3.6.1.4.1.44782.1.4.4.1.42.0 ups1outputUPhaseVoltage 231.9 V WARN: 250V/210V, CRIT: 260V/200V

Bypass Voltage Service

OID Description Example Value Unit Thresholds
.1.3.6.1.4.1.44782.1.4.4.1.59.0 ups1bypassUPhaseVoltage 232.9 V WARN: 250V/210V, CRIT: 260V/200V

Battery Voltage Service

OID Description Example Value Unit Thresholds
.1.3.6.1.4.1.44782.1.4.4.1.19.0 ups1batteryVoltage 217.9 V WARN: 180V, CRIT: 170V

Battery Current Service

OID Description Example Value Unit
.1.3.6.1.4.1.44782.1.4.4.1.20.0 ups1batteryChargingAndDischargingCurrent 0.00 A

Output Current Service

OID Description Example Value Unit
.1.3.6.1.4.1.44782.1.4.4.1.45.0 ups1outputUPhaseCurrent 0.00 A

Temperature Service

OID Description Example Value Unit Thresholds
.1.3.6.1.4.1.44782.1.4.4.1.21.0 ups1batteryTemperature 28.0 °C WARN: 40°C/10°C, CRIT: 45°C/5°C

Input Frequency Service

OID Description Example Value Unit Thresholds
.1.3.6.1.4.1.44782.1.4.4.1.24.0 ups1inputUPhaseFrequency 50.0 Hz WARN: 51Hz/49Hz, CRIT: 52Hz/48Hz

Output Frequency Service

OID Description Example Value Unit Thresholds
.1.3.6.1.4.1.44782.1.4.4.1.40.0 ups1outputFrequency 50.0 Hz WARN: 51Hz/49Hz, CRIT: 52Hz/48Hz

Bypass Frequency Service

OID Description Example Value Unit Thresholds
.1.3.6.1.4.1.44782.1.4.4.1.57.0 ups1bypassFrequency 50.0 Hz WARN: 51Hz/49Hz, CRIT: 52Hz/48Hz

Output Power Service

OID Description Example Value Unit
.1.3.6.1.4.1.44782.1.4.4.1.48.0 ups1outputUPhaseActivePower 0.00 W

Output Load Service

OID Description Example Value Unit Thresholds
.1.3.6.1.4.1.44782.1.4.4.1.51.0 ups1outputUPhaseLoadRate 0.0 % WARN: 80%, CRIT: 90%

Configuration OIDs (Used for Dynamic Defaults)

The device provides configuration thresholds that the plugin uses as dynamic defaults when available:

OID Description Example Value Used In Service
.1.3.6.1.4.1.44782.1.1.3.1.0 inputVoltUpConfig 242 Input Voltage
.1.3.6.1.4.1.44782.1.1.3.2.0 inputVoltLowConfig 187 Input Voltage
.1.3.6.1.4.1.44782.1.1.3.3.0 outputVoltUpConfig 225 Output Voltage
.1.3.6.1.4.1.44782.1.1.3.4.0 outputVoltLowConfig 215 Output Voltage
.1.3.6.1.4.1.44782.1.1.3.5.0 upsTempUpConfig 40 Temperature
.1.3.6.1.4.1.44782.1.1.3.6.0 upsOutputLoadUpConfig 0 Output Load
.1.3.6.1.4.1.44782.1.1.3.7.0 upsBatteryVoltLowConfig 180 Battery Voltage

Data Conversions

The plugin performs the following conversions:

  • Enterprise string values: Parsed as floats (e.g., "231.9" → 231.9)
  • Minutes to seconds: Battery runtime converted for consistent time metrics
  • Status mappings: Integer values mapped to descriptive strings
  • Alarm flags: 0/1 values interpreted as normal/alarm states

Status Value Mappings

Battery Status (upsBatteryStatus)

  • 1: unknown
  • 2: batteryNormal
  • 3: batteryLow
  • 4: batteryDepleted

Output Source (upsOutputSource)

  • 1: other
  • 2: none
  • 3: normal
  • 4: bypass
  • 5: battery
  • 6: booster
  • 7: reducer

Power Supply Mode (ups1powerSupplyMode)

  • 1: standby
  • 2: online
  • 3: battery
  • 4: bypass
  • 5: eco

Base Output Status (upsBaseOutputStatus)

  • 1: unknown
  • 2: onLine
  • 3: onBattery
  • 4: onSmartBoost
  • 5: timedSleeping
  • 6: softwareBypass
  • 7: off
  • 8: rebooting
  • 9: switchedBypass
  • 10: hardwareFailureBypass
  • 11: sleepingUntilPowerReturn
  • 12: onSmartTrim
  • 13: ecoMode
  • 14: hotStandby
  • 15: onBatteryTest

Service Summary

The plugin creates 18 CheckMK services:

  1. UPS System Info - Static information and configuration
  2. UPS Battery Status - Combined battery health, charge, runtime, and alarms
  3. UPS Battery Charge - Individual battery charge percentage monitoring
  4. UPS Battery Runtime - Individual battery runtime remaining monitoring
  5. UPS Power Status - Power source and operational mode
  6. UPS Alarm Status - System alarms and warnings
  7. UPS Input Voltage - AC input voltage monitoring
  8. UPS Output Voltage - AC output voltage monitoring
  9. UPS Bypass Voltage - Bypass line voltage monitoring
  10. UPS Battery Voltage - DC battery voltage monitoring
  11. UPS Battery Current - Battery charging/discharging current
  12. UPS Output Current - Output current monitoring
  13. UPS Temperature - System temperature monitoring
  14. UPS Input Frequency - Input frequency monitoring
  15. UPS Output Frequency - Output frequency monitoring
  16. UPS Bypass Frequency - Bypass frequency monitoring
  17. UPS Output Power - Power consumption in watts
  18. UPS Output Load - Load percentage monitoring

Notes

  • The plugin uses enterprise OIDs (44782) as primary data source with RFC 1628 OIDs as fallback
  • All time metrics are stored in seconds (SI base unit)
  • Thresholds can be customized via CheckMK WATO interface
  • Device configuration values are used as dynamic defaults when available
  • Model identified as Wiseway UPS with various capacity ratings (6000VA, 10kVA)