This document lists the SNMP OIDs monitored by the CheckMK plugin for Wiseway UPS devices. The plugin supports both standard RFC 1628 UPS MIB OIDs and enterprise-specific OIDs from vendor 44782.
Implemented OIDs by Service
System Information Service
Shows static UPS system information and configuration.
OID
Description
Example Value
Unit
.1.3.6.1.2.1.33.1.1.2.0
upsIdentModel
"6000VA"
-
.1.3.6.1.2.1.33.1.1.3.0
upsIdentUPSSoftwareVersion
"VER 6.xxx"
-
.1.3.6.1.2.1.33.1.1.4.0
upsIdentAgentSoftwareVersion
"2.0.0"
-
.1.3.6.1.4.1.44782.1.4.4.1.2.0
ups1equipmentManufacturer
"Others"
-
.1.3.6.1.4.1.44782.1.4.1.5.0
systemSerialNumber
"5A1903026810Q9100039"
-
.1.3.6.1.4.1.44782.1.4.4.1.6.0
ups1installationTime
"2020-06-13"
-
.1.3.6.1.4.1.44782.1.4.4.1.8.0
ups1maintenanceExpirationTime
"2022-06-13"
-
.1.3.6.1.4.1.44782.1.4.4.1.9.0
ups1batteryInstallationReplacementTime
"2021-06-13"
-
.1.3.6.1.4.1.44782.1.4.4.1.10.0
ups1nextMaintenanceTimeOfBattery
"2025-06-13"
-
.1.3.6.1.4.1.44782.1.4.4.1.11.0
ups1ratedPower
5000
W
.1.3.6.1.4.1.44782.1.4.4.1.12.0
ups1ratedCapacityOfBattery
100
Ah
.1.3.6.1.4.1.44782.1.4.4.1.14.0
ups1numberOfBatteries
1
-
.1.3.6.1.4.1.44782.1.4.4.1.15.0
ups1numberOfBatteriesInASingleGroup
16
-
Battery Status Service
Monitors battery health, charge level, and runtime.
OID
Description
Example Value
Unit
Thresholds
.1.3.6.1.2.1.33.1.2.1.0
upsBatteryStatus
2 (batteryNormal)
-
-
.1.3.6.1.2.1.33.1.2.2.0
upsSecondsOnBattery
0
seconds
-
.1.3.6.1.4.1.44782.1.4.4.1.16.0
ups1batteryStatus (enterprise)
2
-
-
.1.3.6.1.4.1.44782.1.4.4.1.17.0
ups1batteryTimeRemaining
15
minutes → seconds
WARN: 600s, CRIT: 300s
.1.3.6.1.4.1.44782.1.4.4.1.18.0
ups1remainingCapacityOfBattery
100
%
WARN: 20%, CRIT: 10%
.1.3.6.1.4.1.44782.1.4.4.1.72.0
ups1batteryAbnormal
0
flag
-
.1.3.6.1.4.1.44782.1.4.4.1.73.0
ups1batteryPowered
0
flag
-
.1.3.6.1.4.1.44782.1.4.4.1.74.0
ups1batteryLowVoltage
0
flag
-
Power Status Service
Monitors power source, operational mode, and power failures.
OID
Description
Example Value
Unit
.1.3.6.1.2.1.33.1.4.1.0
upsOutputSource
3 (normal)
-
.1.3.6.1.4.1.44782.1.4.4.1.39.0
ups1powerSupplyMode
2 (online)
-
.1.3.6.1.4.1.935.1.1.1.4.1.1.0
upsBaseOutputStatus
2 (onLine)
-
.1.3.6.1.2.1.33.1.3.1.0
upsInputLineBads
0
count
.1.3.6.1.4.1.44782.1.4.4.1.77.0
ups1inputAbnormal
0
flag
.1.3.6.1.4.1.44782.1.4.4.1.78.0
ups1outputAbnormal
0
flag
.1.3.6.1.4.1.44782.1.4.4.1.80.0
ups1bypassStatus
1
flag
Alarm Status Service
Monitors system alarms and critical conditions.
OID
Description
Example Value
Unit
.1.3.6.1.4.1.44782.1.4.4.1.71.0
ups1abnormalCommunication
0
flag
.1.3.6.1.4.1.44782.1.4.4.1.76.0
ups1temperatureAbnormal
0
flag
.1.3.6.1.4.1.44782.1.4.4.1.79.0
ups1overLoad
0
flag
.1.3.6.1.4.1.44782.1.4.4.1.81.0
ups1fanFailure
0
flag
.1.3.6.1.4.1.44782.1.4.4.1.85.0
ups1shutdownRequest
0
flag
.1.3.6.1.4.1.44782.1.4.4.1.86.0
ups1testInProgress
1
flag
.1.3.6.1.4.1.44782.1.4.4.1.89.0
ups1shutdownImminent
0
flag
.1.3.6.1.4.1.44782.1.4.4.1.93.0
ups1lowBatteryShutdownImminent
0
flag
.1.3.6.1.4.1.44782.1.4.4.1.94.0
ups1systemStatus
1
status
Physical Measurement Services
Input Voltage Service
OID
Description
Example Value
Unit
Thresholds
.1.3.6.1.4.1.44782.1.4.4.1.27.0
ups1inputUPhaseVoltage
231.9
V
WARN: 250V/210V, CRIT: 260V/200V
Output Voltage Service
OID
Description
Example Value
Unit
Thresholds
.1.3.6.1.4.1.44782.1.4.4.1.42.0
ups1outputUPhaseVoltage
231.9
V
WARN: 250V/210V, CRIT: 260V/200V
Bypass Voltage Service
OID
Description
Example Value
Unit
Thresholds
.1.3.6.1.4.1.44782.1.4.4.1.59.0
ups1bypassUPhaseVoltage
232.9
V
WARN: 250V/210V, CRIT: 260V/200V
Battery Voltage Service
OID
Description
Example Value
Unit
Thresholds
.1.3.6.1.4.1.44782.1.4.4.1.19.0
ups1batteryVoltage
217.9
V
WARN: 180V, CRIT: 170V
Battery Current Service
OID
Description
Example Value
Unit
.1.3.6.1.4.1.44782.1.4.4.1.20.0
ups1batteryChargingAndDischargingCurrent
0.00
A
Output Current Service
OID
Description
Example Value
Unit
.1.3.6.1.4.1.44782.1.4.4.1.45.0
ups1outputUPhaseCurrent
0.00
A
Temperature Service
OID
Description
Example Value
Unit
Thresholds
.1.3.6.1.4.1.44782.1.4.4.1.21.0
ups1batteryTemperature
28.0
°C
WARN: 40°C/10°C, CRIT: 45°C/5°C
Input Frequency Service
OID
Description
Example Value
Unit
Thresholds
.1.3.6.1.4.1.44782.1.4.4.1.24.0
ups1inputUPhaseFrequency
50.0
Hz
WARN: 51Hz/49Hz, CRIT: 52Hz/48Hz
Output Frequency Service
OID
Description
Example Value
Unit
Thresholds
.1.3.6.1.4.1.44782.1.4.4.1.40.0
ups1outputFrequency
50.0
Hz
WARN: 51Hz/49Hz, CRIT: 52Hz/48Hz
Bypass Frequency Service
OID
Description
Example Value
Unit
Thresholds
.1.3.6.1.4.1.44782.1.4.4.1.57.0
ups1bypassFrequency
50.0
Hz
WARN: 51Hz/49Hz, CRIT: 52Hz/48Hz
Output Power Service
OID
Description
Example Value
Unit
.1.3.6.1.4.1.44782.1.4.4.1.48.0
ups1outputUPhaseActivePower
0.00
W
Output Load Service
OID
Description
Example Value
Unit
Thresholds
.1.3.6.1.4.1.44782.1.4.4.1.51.0
ups1outputUPhaseLoadRate
0.0
%
WARN: 80%, CRIT: 90%
Configuration OIDs (Used for Dynamic Defaults)
The device provides configuration thresholds that the plugin uses as dynamic defaults when available:
OID
Description
Example Value
Used In Service
.1.3.6.1.4.1.44782.1.1.3.1.0
inputVoltUpConfig
242
Input Voltage
.1.3.6.1.4.1.44782.1.1.3.2.0
inputVoltLowConfig
187
Input Voltage
.1.3.6.1.4.1.44782.1.1.3.3.0
outputVoltUpConfig
225
Output Voltage
.1.3.6.1.4.1.44782.1.1.3.4.0
outputVoltLowConfig
215
Output Voltage
.1.3.6.1.4.1.44782.1.1.3.5.0
upsTempUpConfig
40
Temperature
.1.3.6.1.4.1.44782.1.1.3.6.0
upsOutputLoadUpConfig
0
Output Load
.1.3.6.1.4.1.44782.1.1.3.7.0
upsBatteryVoltLowConfig
180
Battery Voltage
Data Conversions
The plugin performs the following conversions:
Enterprise string values: Parsed as floats (e.g., "231.9" → 231.9)
Minutes to seconds: Battery runtime converted for consistent time metrics
Status mappings: Integer values mapped to descriptive strings
Alarm flags: 0/1 values interpreted as normal/alarm states
Status Value Mappings
Battery Status (upsBatteryStatus)
1: unknown
2: batteryNormal
3: batteryLow
4: batteryDepleted
Output Source (upsOutputSource)
1: other
2: none
3: normal
4: bypass
5: battery
6: booster
7: reducer
Power Supply Mode (ups1powerSupplyMode)
1: standby
2: online
3: battery
4: bypass
5: eco
Base Output Status (upsBaseOutputStatus)
1: unknown
2: onLine
3: onBattery
4: onSmartBoost
5: timedSleeping
6: softwareBypass
7: off
8: rebooting
9: switchedBypass
10: hardwareFailureBypass
11: sleepingUntilPowerReturn
12: onSmartTrim
13: ecoMode
14: hotStandby
15: onBatteryTest
Service Summary
The plugin creates 18 CheckMK services:
UPS System Info - Static information and configuration
UPS Battery Status - Combined battery health, charge, runtime, and alarms