Skip to content

Conversation

@alihamdan
Copy link
Member

Fixes #308

@alihamdan alihamdan added the bug Something isn't working label Jan 6, 2025
@alihamdan alihamdan self-assigned this Jan 6, 2025
Comment on lines 262 to 264
f"Transformer {id!r} with vector group {parameters.vg} does not have have a "
f"brought out neutral on the LV side. The neutral phase 'n' is ignored. If "
f"you meant to use a brought out neutral, use vector group '{correct_vg}'. "
Copy link
Collaborator

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Typo : have have

clock = parameters.phase_displacement

w1_has_neutral = w1.endswith("N")
if phases1 is None:
Copy link
Collaborator

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Should we emit a warning if n is in bus1.phases but w1_has_neutral is False ?

Copy link
Member Author

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

No it is a valid use case. For example, imagine two transformers on the same bus (in the same substation) where one has a brought out neutral and the other doesn't.

@alihamdan alihamdan merged commit a7e8a61 into develop Jan 6, 2025
5 of 6 checks passed
@alihamdan alihamdan deleted the neutral-not-brought-out branch January 6, 2025 14:52
@benoit9126 benoit9126 mentioned this pull request Jan 9, 2025
Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment

Labels

bug Something isn't working

Projects

None yet

Development

Successfully merging this pull request may close these issues.

BUG: The neutral of Dy11 transformer should not be connected

4 participants