Skip to content

Phoenix Contact Classic Line Controllers ILC1x0 and...

High severity Unreviewed Published May 24, 2022 to the GitHub Advisory Database • Updated Jan 30, 2023

Package

No package listedSuggest a package

Affected versions

Unknown

Patched versions

Unknown

Description

Phoenix Contact Classic Line Controllers ILC1x0 and ILC1x1 in all versions/variants are affected by a Denial-of-Service vulnerability. The communication protocols and device access do not feature authentication measures. Remote attackers can use specially crafted IP packets to cause a denial of service on the PLC's network communication module. A successful attack stops all network communication. To restore the network connectivity the device needs to be restarted. The automation task is not affected.

References

Published by the National Vulnerability Database Jun 25, 2021
Published to the GitHub Advisory Database May 24, 2022
Last updated Jan 30, 2023

Severity

High

EPSS score

Exploit Prediction Scoring System (EPSS)

This score estimates the probability of this vulnerability being exploited within the next 30 days. Data provided by FIRST.
(79th percentile)

Weaknesses

Allocation of Resources Without Limits or Throttling

The product allocates a reusable resource or group of resources on behalf of an actor without imposing any restrictions on the size or number of resources that can be allocated, in violation of the intended security policy for that actor. Learn more on MITRE.

CVE ID

CVE-2021-33541

GHSA ID