Description

Unprotected transport of credentials vulnerability in IDEC PLCs (FC6A Series MICROSmart All-in-One CPU module v2.32 and earlier, FC6A Series MICROSmart Plus CPU module v1.91 and earlier, WindLDR v8.19.1 and earlier, WindEDIT Lite v1.3.1 and earlier, and Data File Manager v2.12.1 and earlier) allows an attacker to obtain the PLC Web server user credentials from the communication between the PLC and the software. As a result, the complete access privileges to the PLC Web server may be obtained, and manipulation of the PLC output and/or suspension of the PLC may be conducted.

References

Published by the National Vulnerability Database Dec 24, 2021
Published to the GitHub Advisory Database Dec 25, 2021
Last updated Feb 3, 2023

Severity

High

EPSS score

Exploit Prediction Scoring System (EPSS)

This score estimates the probability of this vulnerability being exploited within the next 30 days. Data provided by FIRST.
(26th percentile)

Weaknesses

Insufficiently Protected Credentials

The product transmits or stores authentication credentials, but it uses an insecure method that is susceptible to unauthorized interception and/or retrieval. Learn more on MITRE.

CVE ID

CVE-2021-20826