Safety mechanisms

Events

There are four levels of event severity:

  • INFO
  • WARNING
  • CRITICAL
  • FATAL

INFO events are informational, and don't indicate a problem.

WARNING events indicate a potential problem which is not yet serious.

CRITICAL events signal imminent contactor opening and escalate to FATAL after a timeout (which differs by event type). To catch intermittent (flapping) faults, a cumulative time buffer increments while the event is active and decrements when cleared; if the buffer fills, the event escalates to FATAL.

FATAL events immediately trigger the contactor opening sequence, and require manual intervention to reset. Unlike the other event types, FATAL events do not clear when the triggering condition stops.

Current limits

The BMS continuously calculates the maximum allowed charge and discharge current in its present state, and these limits are transmitted to the inverter.

The limits are the lesser of several different calculations:

Temperature derating, which linearly tapers the maximum current such that it reaches zero at the maximum temperature limit. The limits are different for charging and discharging, according to the cell chemistry.

State of charge derating

Voltage limits

There are six separate voltage limits, which are defined in reference to the voltage of an individual cell. These limits operate progressively, and are designed to ensure safety whilst making it usually possible to recover a pack that has gone beyond the normal range.

Working limits

The battery's operating range is defined by the working voltage limits, representing 0% and 100% State of Charge (SoC).

Since some inverters prevent discharging below a specific threshold (e.g., 10%), the Minimum SoC setting allows you to define a percentage that will coresspond to the lower voltage limit.

Soft voltage limits

If a cell's voltage goes outside the soft limits, the BMS immediately issues a WARNING. It will also restrict current to prevent further charging (at the upper limit) or discharging (at the lower limit).

The BMS will disconnect the battery if:

  • A current continues to flow against these restrictions.
  • The state persists for more than one hour.

This gives you a chance to correct the problem - if the battery has disconnected, you can restart the BMS, and will have one hour to charge/discharge the battery back into the normal range.

Hard voltage limits

If a cell exceeds its hard voltage limits, the BMS will immediately disconnect the battery. These limits are set to prevent permanent damage to the cell chemistry. Recovery would require bypassing or manually energizing the contactors.

Proceed with caution if you decide to manually recover or recharge the battery.

Response time

The main loop of the BMS runs every 20 milliseconds. It will therefore take at least 20ms for the BMS to react to a change, up to several multiples of 20ms if the signal propagates through the model in stages.

Most operations performed in the main loop should easily complete within the 20ms deadline. However the BMS performs occasional flash memory writes which can take much longer (the worst case block-erase time of the SPI flash chip is 2 seconds). The normal WARNING that occurs if a loop tick overruns is suppressed when flash memory operations are performed.

A system-wide watchdog timer is set up with a 5 second deadline, which gets reset every tick. If the main loop stalls for more than 5 seconds, the chip will reboot and raise a WARNING event.