Tuya Zigbee CT Clamp — Data Point (DP) Mappings

Reference list of observed Tuya DPID mappings for a CT clamp energy sensor using Zigbee cluster 0xEF00. Use to avoid mis-mapping in drivers, gateways, and integrators.

Note: Vendor/model specific. Validate against your device logs.


Confirmed DP Mappings

  • 0x70 — Voltage

    • Scale: ×0.1 V
    • Example: 2353 → 235.3 V
  • 0x6E — Active power (P)

    • Scale: ×1 W
    • Example: 99 → 99 W
  • 0x71 — Apparent power (S)

    • Scale: ×0.01 VA
    • Example: 11823 → 118.23 VA
    • Sanity: S ≈ V × I, so I_est ≈ S/V using V from 0x70
  • 0x6F — Frequency

    • Scale: ×0.01 Hz
    • Example: 4931 → 49.31 Hz
    • Note: Previously misinterpreted as current

Likely/Observed (TBD) DP Mappings

  • 0x65 — Energy counter (units TBD)

    • Hypothesis: Wh or 0.01 kWh
    • Method: Compare Δenergy/Δt versus average P over time
    • Example raw values ~27000 (could be ~27.0 kWh if Wh; ~270.0 kWh if 0.01 kWh)
  • 0x73 — Energy counter (units TBD)

    • Hypothesis: total or mirror of 0x65
    • Check: delta/hour behavior, reset at midnight, or persistent total
  • 0x66 — Enum state/mode

    • Observed: 0
    • Likely: device mode/relay/operational state (no effect seen yet)
  • 0x6A — Temperature (probable)

    • Observed: 23, 28 (plausible °C)
  • 0x72, 0x69 — Flags/thresholds (unclear)

    • Often 0; may represent alarms or thresholds (not active)
  • 0x79 — Unknown percentage-like metric

    • Often 100; may be device-specific indicator

Derived Values (in firmware/integration)

  • Estimated current I_est (A) ≈ S/V using 0x71 and 0x70
  • Power factor PF ≈ P/S using 0x6E and 0x71

Notes

  • Device-specific: These mappings are from observed logs for a particular Tuya CT clamp.
  • Current logging: Firmware logs 0x70 (V), 0x6E (P), 0x71 (S), 0x6F (Hz); 0x65/0x73 raw; derived I≈S/V and PF≈P/S.

Verification Guidance

  • Energy unit confirmation (0x65/0x73):
    • Record P (W) and energy over a known interval.
    • Compute expected Δenergy ≈ average(P) × Δt_hours.
    • Match against raw delta to infer scale (Wh vs 0.01 kWh).
  • Daily reset detection:
    • Track midnight behavior. If counter resets, likely “today” energy; if not, total accumulator.

Mapping Table (experimental)

DPID Name Type Scale Unit Status Notes
0x70 voltage value 0.1 V confirmed
0x6E active_power value 1 W confirmed
0x71 apparent_power value 0.01 VA confirmed I_est ≈ S/V
0x6F frequency value 0.01 Hz confirmed
0x65 energy_counter value TBD Wh or 0.01 kWh likely confirm via Δenergy/Δt vs avg P
0x73 energy_counter_alt value TBD Wh or 0.01 kWh likely total or mirror of 0x65
0x66 mode_state enum likely operational state
0x6A temperature value 1 °C probable
0x72 flags_thresholds bitmap_or_enum unclear often 0
0x69 flags_thresholds_2 bitmap_or_enum unclear often 0
0x79 percent_like_metric value unclear often 100

Derived:

  • current_A ≈ apparent_power_VA / voltage_V
  • power_factor ≈ active_power_W / apparent_power_VA

Contributing

  • Share logs: Raw DPID, payloads, scales, and real-world meter references.
  • Propose fixes: Open PRs to adjust scales, units, or add new DPIDs.
  • Verification checklist: Include Δenergy/Δt vs average P, and reset behaviors.

License

MIT

About

Electrical measurement cluster data points for Tuya zigbee powered ct clamp.