Configuration

Docs: Getting Started | Configuration | API Reference | Architecture | MQTT Topics | SNMP OIDs | Multi-PDU | Security | Troubleshooting | Features

All bridge configuration is done through environment variables in the .env file at the project root. Copy .env.example to .env and edit it. After changing any setting, rebuild and restart the bridge:

./start --rebuild

PDU Connection Settings

These settings tell the bridge how to reach your PDU over SNMP. In single-PDU mode, these are the primary connection settings. In multi-PDU mode, they are overridden by pdus.json (see Multi-PDU below).

Variable Default Description
PDU_HOST 192.168.20.177 IP address or hostname of your PDU
PDU_SNMP_PORT 161 SNMP port (almost always 161)
PDU_COMMUNITY_READ public SNMP v2c community string for read (GET) operations
PDU_COMMUNITY_WRITE private SNMP v2c community string for write (SET) operations -- used for outlet control
PDU_DEVICE_ID (empty) Unique identifier used in MQTT topics (pdu/{device_id}/...) and the web UI. Auto-assigned as pdu-01, pdu-02, etc. if left empty. Must not contain / # + or spaces.

Example:

PDU_HOST=192.168.1.50
PDU_SNMP_PORT=161
PDU_COMMUNITY_READ=public
PDU_COMMUNITY_WRITE=private
PDU_DEVICE_ID=rack1-pdu

Serial Transport Settings

These settings enable RS-232 serial console access for full PDU management (thresholds, ATS, network, security, notifications). Serial is optional -- SNMP works for monitoring and outlet control without it.

Variable Default Description
PDU_SERIAL_PORT (empty) Serial device path (e.g., /dev/ttyUSB0). Leave empty to disable serial.
PDU_SERIAL_BAUD 9600 Serial baud rate
PDU_SERIAL_USERNAME cyber Serial console login username (CyberPower factory default is cyber)
PDU_SERIAL_PASSWORD cyber Serial console login password (CyberPower factory default is cyber)
PDU_TRANSPORT snmp Primary transport: snmp, serial, or both

Example:

PDU_SERIAL_PORT=/dev/ttyUSB0
PDU_SERIAL_BAUD=9600
PDU_SERIAL_USERNAME=cyber
PDU_SERIAL_PASSWORD=mypassword

When both SNMP and serial are configured, the bridge uses SNMP as the primary transport for monitoring (faster) and serial for management operations. If one transport fails, the bridge automatically falls back to the other.


MQTT Settings

These control how the bridge connects to the MQTT broker (Mosquitto).

Variable Default Description
MQTT_BROKER 127.0.0.1 Hostname or IP of the MQTT broker. The Docker Compose file overrides this to 127.0.0.1 because the bridge uses network_mode: host. The .env value is only used when running the bridge outside Docker.
MQTT_PORT 1883 MQTT broker port
MQTT_USERNAME (empty) Username for MQTT authentication. Leave empty for anonymous access.
MQTT_PASSWORD (empty) Password for MQTT authentication. Leave empty for anonymous access.

Anonymous access (default):

MQTT_BROKER=mosquitto
MQTT_PORT=1883

Authenticated access:

MQTT_BROKER=mosquitto
MQTT_PORT=1883
MQTT_USERNAME=pdu-bridge
MQTT_PASSWORD=your-secure-password

When you set MQTT_USERNAME and MQTT_PASSWORD, the bridge will authenticate with the broker on connect. You also need to configure your Mosquitto broker to require authentication -- see Security for instructions.


Bridge Operation Settings

These control how the bridge itself behaves.

Variable Default Range Description
BRIDGE_POLL_INTERVAL 1.0 0.1 - 300 Seconds between SNMP poll cycles. 1.0 means the bridge queries the PDU once per second.
BRIDGE_MOCK_MODE false true/false Use simulated PDU data instead of real SNMP. Useful for development and demos.
BRIDGE_LOG_LEVEL INFO DEBUG, INFO, WARNING, ERROR Python logging level. Set to DEBUG for troubleshooting.
BRIDGE_SNMP_TIMEOUT 2.0 0.5 - 30 Seconds to wait for each SNMP response before timing out.
BRIDGE_SNMP_RETRIES 1 0 - 5 Number of times to retry a failed SNMP request.
BRIDGE_WEB_PORT 8080 1 - 65535 Port for the web dashboard and REST API.
BRIDGE_RULES_FILE /data/rules.json file path Path to the automation rules JSON file (inside the container).
BRIDGE_PDUS_FILE /data/pdus.json file path Path to the multi-PDU configuration file (inside the container).
BRIDGE_OUTLET_NAMES_FILE /data/outlet_names.json file path Path to custom outlet name overrides (inside the container).
BRIDGE_WEB_PASSWORD (empty) string Set to enable web UI authentication. When set, all API endpoints require a session token.
BRIDGE_WEB_USERNAME admin string Username for web UI login (only used when BRIDGE_WEB_PASSWORD is set).
BRIDGE_SESSION_SECRET (auto-generated) string Secret key for session tokens. Auto-generated if empty. Set explicitly for consistent sessions across restarts.
BRIDGE_SESSION_TIMEOUT 86400 60 - 604800 Session token lifetime in seconds (default: 24 hours).
BRIDGE_RECOVERY_ENABLED true true/false Enable DHCP resilience -- auto-recover via subnet scan when the PDU changes IP.
BRIDGE_SETTINGS_FILE /data/bridge_settings.json file path Path to persisted runtime settings (inside the container).

History and Reports Settings

These control the SQLite history database and PDF energy reports.

Variable Default Range Description
HISTORY_RETENTION_DAYS 60 1 - 365 How many days of 1Hz history to keep. Older data is automatically deleted hourly.
HOUSE_MONTHLY_KWH 0 0 - 100,000 Your household's monthly electricity usage in kWh. Set to 0 to disable.
BRIDGE_HISTORY_DB /data/history.db file path Path to the SQLite database file (inside the container).
BRIDGE_REPORTS_ENABLED true true / false Enable or disable automatic PDF report generation.
BRIDGE_REPORTS_DIR /data/reports directory path Where generated PDF reports are stored (inside the container).
BRIDGE_REPORTS_PATH ./reports host path Host directory bind-mounted to /data/reports in Docker. Reports are directly accessible here for backup or file sharing.

Storage estimate: At 1Hz with 2 banks and 10 outlets, the database grows by roughly 50-100 MB per month. With the default 60-day retention, expect the database to stabilize around 100-200 MB. PDF reports are ~30-50 KB each and are never automatically deleted.


InfluxDB Settings

These configure the optional InfluxDB time-series database. InfluxDB is not required -- the bridge stores 60 days of history in SQLite by default. InfluxDB is useful for longer retention, advanced queries, or Grafana dashboards.

Variable Default Description
INFLUXDB_URL http://influxdb:8086 InfluxDB URL
INFLUXDB_ORG cyber-pdu InfluxDB organization
INFLUXDB_BUCKET pdu InfluxDB bucket name
INFLUXDB_ADMIN_USER admin Initial admin username (set during first run)
INFLUXDB_ADMIN_PASSWORD changeme123 Initial admin password -- change this in production
INFLUXDB_ADMIN_TOKEN cyber-pdu-admin-token API token for Telegraf writes -- change this in production

Telegraf Settings

Variable Default Description
TELEGRAF_MQTT_BROKER tcp://mosquitto:1883 MQTT broker URL for Telegraf's MQTT consumer input

Multi-PDU: pdus.json Format

For monitoring multiple PDUs from a single bridge instance, create a pdus.json file. This file takes priority over the single-PDU environment variables (PDU_HOST, etc.).

The file is stored at the path specified by BRIDGE_PDUS_FILE (default: /data/pdus.json). Since the bridge container mounts the bridge-data Docker volume at /data, you can either:

  1. Use the ./wizard script to generate the file interactively.
  2. Use the REST API (POST /api/pdus) to add PDUs at runtime.
  3. Create it manually inside the container's data volume.

pdus.json structure

{
  "pdus": [
    {
      "device_id": "rack1-pdu",
      "host": "192.168.20.177",
      "snmp_port": 161,
      "community_read": "public",
      "community_write": "private",
      "label": "Main Rack PDU",
      "enabled": true,
      "num_banks": 2
    },
    {
      "device_id": "rack2-pdu",
      "host": "192.168.20.178",
      "snmp_port": 161,
      "community_read": "public",
      "community_write": "private",
      "label": "Secondary Rack PDU",
      "enabled": true,
      "num_banks": 2
    }
  ]
}

Field reference

Field Required Default Description
device_id Yes -- Unique identifier. Used in MQTT topics and API queries. Must not contain / # + or spaces.
host Yes -- IP address or hostname of the PDU
snmp_port No 161 SNMP port
community_read No public SNMP read community string
community_write No private SNMP write community string
label No "" Human-friendly display name
enabled No true Set to false to skip this PDU without removing it from the config
num_banks No 2 Default bank count (auto-detected from SNMP at startup if available)
serial_port No "" Serial device path (e.g., /dev/ttyUSB0) for management access
serial_baud No 9600 Serial baud rate
serial_username No "admin" Serial console login username
serial_password No "cyber" Serial console login password
transport No "snmp" Primary transport: "snmp", "serial", or "both"

See Multi-PDU for the full setup guide.


Automation Rules Reference

Automation rules let the bridge automatically control outlets based on voltage thresholds, ATS source status, or time-of-day schedules. Rules are stored in rules.json (path configured by BRIDGE_RULES_FILE).

You can manage rules through:

  • The web dashboard's Automation panel
  • The REST API (GET/POST /api/rules, PUT/DELETE /api/rules/{name})
  • Direct editing of the JSON file

Rule structure

{
  "name": "low-voltage-shutoff",
  "input": 1,
  "condition": "voltage_below",
  "threshold": 108,
  "outlet": 5,
  "action": "off",
  "restore": true,
  "delay": 5,
  "enabled": true,
  "days_of_week": [0, 1, 2, 3, 4],
  "schedule_type": "continuous"
}

Rule fields

Field Required Default Description
name Yes -- Unique name for the rule
input No 0 Which input source to monitor: 1 = Source A, 2 = Source B. Ignored for time-based conditions.
condition Yes -- Trigger condition (see table below)
threshold Yes -- Condition threshold: voltage in volts (float), time as "HH:MM", or time range as "HH:MM-HH:MM"
outlet Yes -- Outlet number (1-based), comma-separated list ("1,3,5"), or range ("1-4")
action Yes -- Action when triggered: "on" or "off"
restore No true Reverse the action when the condition clears
delay No 5 Seconds the condition must hold before the rule fires
enabled No true Set to false to disable without deleting
days_of_week No null Array of day numbers (0=Mon, 6=Sun). null = every day.
schedule_type No "continuous" "continuous" (re-arms) or "oneshot" (auto-disables after firing once)

Available conditions

Condition Threshold Format Description
voltage_below Float (volts) Triggers when source voltage drops below threshold
voltage_above Float (volts) Triggers when source voltage rises above threshold
ats_source_is Integer (1 or 2) Triggers when the active ATS source matches (1=A, 2=B)
ats_preferred_lost (ignored) Triggers when the ATS has transferred away from the preferred source
time_after "HH:MM" Triggers after the specified time of day
time_before "HH:MM" Triggers before the specified time of day
time_between "HH:MM-HH:MM" Triggers during the time range. Supports midnight wrapping (e.g., "22:00-06:00")

Example rules

Turn off non-essential equipment during a brownout:

{
  "name": "brownout-protection",
  "input": 1,
  "condition": "voltage_below",
  "threshold": 108,
  "outlet": 5,
  "action": "off",
  "restore": true,
  "delay": 10
}

Night-mode: turn off lab lights after hours:

{
  "name": "night-mode-lights",
  "input": 0,
  "condition": "time_between",
  "threshold": "22:00-06:00",
  "outlet": 8,
  "action": "off",
  "restore": true,
  "delay": 0
}

Alert when ATS switches to backup power:

{
  "name": "backup-power-shed",
  "input": 0,
  "condition": "ats_preferred_lost",
  "threshold": 0,
  "outlet": 10,
  "action": "off",
  "restore": true,
  "delay": 5
}

Home Assistant Setup

The bridge automatically publishes MQTT Discovery configuration to Home Assistant when it starts. No manual configuration is needed if your Home Assistant instance is connected to the same MQTT broker.

What gets auto-discovered

Entity Type Count Description
Switches 1 per outlet On/off control for each outlet
Sensors 6 per bank Voltage, current, power, apparent power, power factor, load state
Sensors 2 (input) Input voltage, input frequency
Binary sensor 1 Bridge online/offline status

Requirements

  1. Home Assistant must have the MQTT integration configured and connected to the same Mosquitto broker.
  2. MQTT Discovery must be enabled (it is enabled by default in Home Assistant).

How it works

On startup, the bridge publishes retained configuration messages to homeassistant/switch/..., homeassistant/sensor/..., and homeassistant/binary_sensor/.... Home Assistant picks these up automatically and creates the corresponding entities.

The device appears in Home Assistant under the name CyberPower {DEVICE_ID} with the model detected from the PDU's SNMP identity.


Outlet Naming

You can assign custom names to outlets through the web dashboard or the REST API. Custom names override the names stored on the PDU hardware and persist across restarts.

Via the web dashboard

Click the pencil icon next to any outlet name in the dashboard to rename it.

Via the REST API

# Set a custom name
curl -X PUT http://localhost:8080/api/outlets/1/name \
  -H 'Content-Type: application/json' \
  -d '{"name": "File Server"}'

# Clear a custom name (reverts to PDU hardware name)
curl -X PUT http://localhost:8080/api/outlets/1/name \
  -H 'Content-Type: application/json' \
  -d '{"name": ""}'

# List all custom names
curl http://localhost:8080/api/outlet-names

Custom names are saved to a JSON file at the path specified by BRIDGE_OUTLET_NAMES_FILE (default: /data/outlet_names.json). In multi-PDU mode, each PDU gets its own outlet names file (/data/outlet_names_{device_id}.json).